background image

wATEr COIl OPTION

Example 1:

 Thermo-siphon Method. This is the simplest and most economical method, providing the existing 

water heater (storage tank) is within 10 feet of the stove. The water inlet, where the Temp/Pressure relief valve 

is located, must be higher than the top leg of the water coil. The storage tank should be elevated, if necessary, 

to allow for proper thermo-siphon action.

A). Turn off the water heater and the water supply to it. Drain the tank completely.

B). Remove the Temp/Pressure relief valve and discard. Install a short ¾” nipple and tee (1) along with a new 

Temp/Pressure relief valve.

C). Run ¾” copper tubing, along with the necessary fittings, between the storage tank and the top leg of the 

coil. Install a ¾” vent elbow and automatic “float type” air vent (2) in the high point of the line. Within two feet 

of the top leg of the coil, install a 150 lb. pressure relief valve (7). Run ¾” tubing from the release exit of both 

relief valves, downward (3) so that the hot water may escape in the event of over-heating.

D). Remove the drain valve, at the bottom of the storage tank. Install a ¾” nipple and tee, and reinstall the 

drain valve to the tee (4). Run ¾” copper tubing, with the necessary fittings, between the drain/tee combination 

and the lower leg of the coil. 

After all of the connections are com-

pleted, you can refill the tank. Restore 

power to the water heater ONLY after 

the tank has been completely refilled.

Example 2:

 Circulating pump method. 

Used when the distance is more than 

ten feet or when the stove is on a higher 

level than the existing water heater. In 

addition to a circulator, you may want 

to add a aquastat to control the pump 

according to water temperature. This is 

not necessary if the circulator is left run 

continuously. Another option is a gate valve placed near the circulator to control the rate of flow.

A). Turn off the water heater and the water supply to it. Drain the tank completely.

B). Remove the Temp/Pressure relief valve and discard. Install a short ¾” nipple and tee (1) along with a new 

Temp/Pressure relief valve.

C). Remove the drain valve, at the bottom of the storage tank. Install a ¾” nipple and tee, and reinstall the 

drain valve to the tee (4).

D). Install a circulating pump (6) as shown. Run ¾” copper tubing from the circulator to the lower leg of the coil. 

This is where the optional gate valve (5) can be installed.

E). Install a ¾” tee and a 150 lb. pressure relief valve (7) in the top leg within 2 feet of the top outlet of the wa

-

ter coil.

F). Complete the copper line by running it back to the tee at the top of the water tank, making sure to install a 

vent elbow and automatic air vent (2) at the high point of the line. The optional aquastat can be installed in this 

line a maximum of six feet from the stove. The aquastat must be a “close on temperature rise” type and must 

be wired and set to turn on the circulator when the water temperature reaches 120˚ Farenheit. 

The system is now ready to be refilled and power restored to the water heater ONLY after the tank is filled.

EXAmPlE 2: Circulator 

method. (more than 10 feet.)

Summary of Contents for 3-90-70738

Page 1: ...MAY RESULT FOR YOUR SAFETY FOL LOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Contact your local authority such as municipal building department fire department fire prevention bureau etc to determine the need for a permit Cette guide d utilisation est disponible en francais Chez votre concessionnaire de...

Page 2: ... Table of Contents Safety Considerations 3 Assembly 4 Installation 5 Chimney Venting 6 Operating Instructions 8 Preventative Maintenance 9 Optional Hot Water Coil 10 Warranty 12 Testing Label 13 ...

Page 3: ...erate It has been verified that creosote will ignite at 650 degrees fahrenheit It is the owner s responsibility to follow these recommenda tions This stove consumes air when it is burning if your house is tightly sealed and insulated it is advisable that a window in the vicinity be opened slightly while the stove is burning Information contained in this manual is man ufacturer s recommendations an...

Page 4: ... The shaker handle installs onto the shaker handle mount using the two hex bolts and washers provided Firebricks The SF250 uses 14 standard firebricks as shown below These standard firebricks measure 9 X 4 X 1 each The firebricks are already installed in the stove but can be removed to lighten the stove for moving The doors can also be removed by simply lift ing them off of the hinges ...

Page 5: ...should con sist of 3 8 millboard or a stove board providing equal protection k 84 R 45 The floor protection should extend 8 to the rear and either side and 16 in front of the stove The floor protection should also extend 2 to either side of the chimney connector to the wall where the connector enters the flue 36 8 36 8 8 16 24 Floor Protection Floor Protection Adjustable Leveling Feet To accomodat...

Page 6: ... from the stove collar The chimney must be two feet higher than anything within ten feet It also must extend three feet above the point where it intersects or exits the roof line In order to have a properly operating solid fuel heat ing system the chimney must be capable of provid ing the necessary draft The minimum required draft is 06 inches of water column W C This must be measured using a draf...

Page 7: ...ould be no more than two 90 elbows or the equivalent used in connecting the stove to the chimney flue H Shared Flue No more than one appliance shall vent into a single flue The most common cause of poor draft is an improp erly sized flue liner It is recommended that the inside Wind direction dimensions of the liner be at least as large as the ap pliance flue outlet and no larger than 125 of the co...

Page 8: ...ime in between Loading Coal should only be added when there is a reasonably hot fire The coal bed should be bright and vigorous If the fire is burning hot and there is a deep bed of coals full loads can be added If it is not as described add coal in small batches only Increasing Heat From A Low Fire Every effort should be made not to let a coal fire burn so long that it has started to die This wil...

Page 9: ...y any debris will be at the bottom by the clean out door Open the clean out and vacuum the loose debris Clean the smoke pipe from the chimney to the stove using a metal brush Cleaning of the spiral chamber Remove clean out plate from the front of the stove Using a 3 4 wrench loosen the clean out bolt approximately 2 turns Slide the clean out plate to one side and remove it from the opening Scrape ...

Page 10: ... supplied nuts on each leg of the coil Place the coil through the holes in the stove and adjust the nuts so that the pipes stick out about 1 to 1 from the sidewall of the stove Put flat wash ers and nuts on the outside and tighten within inch Place fiberglass gasket around each pipe at the washers and tighten securely You are now ready to run pipes according to one of the follow ing examples EXAMP...

Page 11: ... 2 Circulating pump method Used when the distance is more than ten feet or when the stove is on a higher level than the existing water heater In addition to a circulator you may want to add a aquastat to control the pump according to water temperature This is not necessary if the circulator is left run continuously Another option is a gate valve placed near the circulator to control the rate of fl...

Page 12: ...e not covered Damage and or repairs including but not limited to remote controls filters fuses knobs glass ceramic brick panels ceramic fiber afterburners door packing tile ceramic log sets paint batteries or battery back up and related duct work are not covered Also excluded from this warranty are consumable or normal wear items including but not limited to flame guides grates coal bars afterburn...

Page 13: ...13 testing label ...

Reviews: