HI 2160RC
PLUS
MANUAL
4-2
•
4.The dip switch is located on the underside of the top panel.
Speed Control Output
Card (Prt. #0535-0406)
•
The control output card transmits the Rate of Change (ROC) cur-
rent and voltage signals to the motor controller.
•
Both the current and voltage outputs are simultaneously available
and can be used for different devices. There is a restriction how-
ever, one of the outputs must be dedicated to the feeder motor con-
trol and must be configured to match the inputs of the motor
control.
•
Jumper Settings: (See Fig. 4-1)
TABLE 4-1: CONTROL OUTPUT JUMPER SETTINGS
JUMPER CONFIGURATION CHART
Current Selection
Voltage Selection
Configuration
0 - 24 mA
4 - 24 mA
Jumper
W1
W2
Configuration
0 - 5 VDC
0 - 10 VDC
Jumper
W3
W4
•
Potentiometers
Voltage Zero - R4
Voltage Span - R16
Current Span - R5
Current Zero - R19
•
The potentiometers are calibrated and adjusted at the factory. No
further adjustment is necessary.
•
Should additional adjustments be desired, contact
Hardy Process
Solutions
Customer Service Department for adjustment
information.
•
See Chapter 3 for installation instructions.