Set Probe
Here
Set Probe
Here
Chapter 9 - Torubleshooting and Repair
9-9
FIG. 9-4 USING A VOLTMETER TO CHECK LOAD CELL VOLTAGE
Result 1. If the voltage fluctuates with the weight the problem is exter-
nal.
Result 2. If the voltage does not fluctuate with the weight, call your
local representative or
Hardy Process Solutions
Customer Support Department.
Feeder Motor Won't Start
TROUBLE
PROBABLE CAUSE
REMEDY
When pushing the Start
button it does not acti-
vate the motor controller
(Analog Control) on the
feeder.
1.
Wiring to Analog Control
Connector is incorrect.
2.
Output configuration
jumpers are not set cor-
rectly for the feed back
signal.
3.
Feeder motor malfunc-
tion.
1. Check the wiring to the
Control Output con-
nector: (See Fig. 9-5)
For Jumper Settings
See Chapter 4)
Pin 1 = +Voltage
Pin 2 = -Voltage
Pin 5 = -Current
Pin 6 = +Current
2. Check the jumper set-
tings on the Control
Output board. (Prt.
#0535-0406) (See Fig.
9-6)
3. Switch the controller to
manual operating
mode. (See Chapter 7
for instructions)