HANYOUNG NUX TPR-3N Instruction Manual Download Page 3

Safety information

Before using the product, please read the safety information thoroughly and use it properly.

Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality.

Suffix code

Model

Code

Content

TPR-3N

□ □ □

3 phase power regulator (no indication function)

Power 

supply 

voltage

220

220 VAC 

380

380 VAC    

440

440 VAC 

Rated Current

70

70 A

100

100 A

Input

side

Load

side

External

volume

Alarm

output

ON/OFF

Control

input

5

6

7

3 4

5 6 7

4

5

3

5

8

9

3

9

8

5

6

7

5 6 7

4

-

20

mA

DC

+

-

External

VR

10

K

External

VR

10

K

ALM

RUN/STOP

1

-

5

V

DC

ON/OFF

1

5

7

11

3

12

10

6

2

1 2

5 6 7

10 11 12

+

-

External

VR

10

K

Dimension 

Connection diagram

█ Terminal arrangem

[unit : mm]

DANGER

DANGER indicates an imminently hazardous situation which, 

if not avoided, will result in death or serious injury

WARNING

WARNING indicates a potentially hazardous situation which, 

if not avoided, could result in death or serious injury

CAUTION

CAUTION indicates a potentially hazardous situation which, 

if not avoided, may result in minor or moderate injury

• The input/output terminals are subject to electric shock risk.

  Never let the input/output terminals come in contact with your body or conductive   

  substances.

Danger

• If this product is used with the machinery which may be caused human injury or serious  

  property damage then use it after surely installing the protection equipment for two or   

  three times.

• To prevent defection or malfunction of this product, supply proper power voltage in 

  accordance with the rating.

• To prevent electric shock or malfunction of product, do not supply the power until the 

   wiring is completed.

• Do not decompose, modify, revise or repair this product. This may be a cause of 

  malfunction, electric shock or fire.

• Reassemble this product while the power is OFF. Otherwise, it may be a cause of 

    malfunction or electric shock.

Warning

• The place of operating this product affect to the its functions and life cycle so that avoid 

  to use it in the following circumstance.

- A place of having high humidity and not circulating air

- A place of piling dust or impurity or having high ambient temperature or high vibration

• The contents of this manual may be changed without prior notification.

• Make sure that there is no damage or abnormality of the product during delivery.

• After turning OFF power sources of all instruments, please wire them.

• The Thyristor Power Regulator shall be installed perpendicularly.

• Install exhausting fan in internal and upside of the panel.

• Tighten BOLT of the input and output wire enough.

• Do not use this product at any place with corrosive (especially noxious gas or ammonia) 

  or  flammable gas.

• Do not use this product at any place with direct vibration or impact.

• Do not use this product at any place with liquid, oil, medical substances, dust, salt or 

  iron  contents. (Use at Pollution level 1 or 2)

• Do not polish this product with substances such as alcohol or benzene.

• Do not use this product at any place with a large inductive difficulty or occurring static 

   electricity or magnetic noise.

• Do not use this product at any place with possible thermal accumulation due to direct 

   sunlight or heat radiation.

• Install this product at place under 2,000 m in altitude.

• When the product gets wet, the inspection is essential because there is danger of an 

   electric leakage or fire.

• Do not connect anything to the unused terminals.

• After checking the polarity of terminal, connect wires at the correct position.

• The warranty period for this product including parts is one year if this product is 

  properly used.

•When installing more than 1 devices close to each other, must have gap at least 100 ㎜.

Caution

Specification

Power supply voltage

220 VAC,  380 VAC,  440 VAC

Operating Frequency

50 / 60 ㎐(Dual usage)

Rated Current

70 A / 100 A

Protective circuit

Protected by the internal fuse

Applying load

Resistance load / inductive load (Select by conversion switch)

Control 

input

Current input

4 - 20 ㎃ DC

Voltage input

0 - 5 VDC, 1 - 5 VDC, 0 - 10 VDC

Contact input

ON/OFF

External V.R

External volume (10 KΩ)

Control method

Phase control,  ON/OFF control (Switch selection)

Starting method

SOFT START / SOFT UP / DOWN

Output adjusting range Above 95 % of input voltage (when applying max current input)

Cooling method

Forced cooling

Indicating method

Indicate the output by LED 

Insulation Resistance

Min. 100 ㏁ (500 VDC Mega standard)

Output adjusting range

0 ~ 100 % (Adjust the V.R or parameter value.)

Dielectric Strength

For 1 minute at 2000 VAC 50/60 ㎐

Line noise

Noise (2 ㎸) by the noise simulator

Ambient temperature

0 ~ 50 ℃ (Without condensation)

Ambient humidity

35 ~  85 % R.H.

Storage temperature

-25 ~ 70 ℃

Weight

Approx. 5 ㎏

   3Phase Power Regulator

 

TPR-3N

 

(70 A / 100 A)

 

       Thank you for purchasing HANYOUNG product.

 

Please check whether the product is the exactly same as you ordered.

 

Before using the product, please read this instruction manual carefully.

 

Please keep this manual where you can view at any time.

 INSTRUCTION MANUAL

28, Gilpa-ro 71beon-gil, Michuhol-gu, 

Incheon, Korea

TEL : +82-32-876-4697 

http://www.hynux.com

HANYOUNGNUX CO.,LTD

HEAD OFFICE

MB0301KE190718

Reviews: