background image

Model

Code

Content

SSR-

□ □ □ □ □ Solid State Relay

Phase

2

Single-Phase

C

2 contacts

Rated load current

25

25A

40

40A

Operating load voltage

2

90 - 264 V a.c.

Operation method

Z

Zero-cross switching

Model

SSR-2C252Z

SSR-2C402Z

Loa

d

Operating load voltage

90 - 264 V a.c.

Peak voltage (non-repetition)

600 V

Rated load current

25 A

40 A

Frequency

50/60 Hz (dual usage)

Surge current

 

(8.3 ms non-repetition)

260 A

420 A

Leakage current

Max. 10 mA

Output ON voltage drop

Max. 1.8 V (RMS)

Input

Operating voltage range

4 - 32 V d.c.

Impedance

Max. 4 ㏀

Operating voltage

Min. 3 V d.c.

Reset voltage

Max. 1.5 V d.c.

Response speed

Max. 1/2 Cycle + 1 ms

Insulation resistance

500 V d.c. 100 ㏁ (input/output and among cases)

Dielectric strength

2,500 V a.c. (60 ㎐ for one minute)

Vibration resistance

10 -55 Hz, double amplitude: 1.5 mm, each X· Y· Z axis for 2 hours

Shock resistance

1,000  , each X· Y· Z axis for 3 times

Storage temperature

-30 ~ 90 ℃

Ambient temperature

-20 ~ 80 ℃ (without condensation)

Ambient humidity

45 ~ 85 % R.H.

Applied standard

IEC 62314

Load Category

LC A

IP Degree

IP20

Pollution degree

2 Rating

Weight (g)

Approx. 670 (box included)

Approx. 900 (box included)

■ 25 A

■ 40 A

▍Suffix code

▍Part names

▍Specifications

▍Dimensions

[Unit : mm]

INPUT

POWER

NC

NC

AL 80 ℃ (B)

+C1

-C2

+B1

-B2

BI AL (A)

AL COM

MADE IN KOREA

SSR-2B252Z

SOLID STATE RELAY

LOAD : 

90 - 264 VAC 25 A

INPUT : 

4 - 32 VDC 12 mA






INPUT

NC

NC

NC

AL 60 ℃

(B)

+C1

-C2

NC

MADE IN KOREA

SSR-2C252Z

SOLID STATE RELAY

LOAD : 

90 - 264 VAC 25 A

INPUT : 

4 - 32 VDC 12 mA






AL 80 ℃

(B)

No.

Content

Load power input terminal


Temperature control signal 

(4 - 32 V d.c.)


Alarm 1 (at a heat sink 

temperature of 60 ℃)

"B contact" internal 

bimetallic contact

Alarm 2 (at a heat sink 

temperature of 80 ℃)

"B contact" internal 

bimetallic contact


NC (not used)

LOAD terminal


Status indicator LED

Status

Alarm output

Max. 

60℃

Normal 

operation

AL60°C, AL80 °C 

contact close

Min. 60℃  Alarm output

AL60° C 

contact open

Min. 80℃  Alarm output

AL80 °C 

contact open

● Part names

● Alarm output

Name LED Color

Content

INPUT

Green

Lights up when temperature 

control voltage is applied

● Status indicator LED description

※ This product is not equipped with an internal fuse. 

      It is recommended to use a fast fuse separately outside, as shown in the picture. 

■ Load Current Characteristics

■ Input Current Characteristics

- All insulation circuit configuration for each

   terminal function (temperature control part, alarm part)

INPUT

POWER

NC

NC

AL 80 ℃ (B)

+C1

-C2

+B1

-B2

BI AL (A)

AL COM

MADE IN KOREA

SSR-2B252Z

SOLID STATE RELAY

LOAD : 

90 - 264 VAC 25 A

INPUT : 

4 - 32 VDC 12 mA

INPUT

NC

NC

NC

AL 60 ℃

(B)

+C1

-C2

NC

MADE IN KOREA

SSR-2C252Z

SOLID STATE RELAY

LOAD : 

90 - 264 VAC 25 A

INPUT : 

4 - 32 VDC 12 mA

AL 80 ℃

(B)

Load voltage

LOAD

PLC

▍Connection example

▍Load / Input current characteristics

▍Installation method

▍Installation interval

0

50

100

150

200

250

300

350

400

10

100

1

1000

50
40
30
20
10

-30 -20 0

20 40

60 80 100

SSR-2C40

SSR-2C25

 SSR-2C40

SSR-2C25

Lo

ad curr

ent (A)

Ambient temperature (℃)

0

50

100

150

200

250

300

350

400

10

100

1

1000

50
40
30
20
10

-30 -20 0

20 40

60 80 100

SSR-2C40

SSR-2C25

 SSR-2C40

SSR-2C25

Input curr

ent (A)

Frequency (60 Hz)

• Be sure to install the SSR vertically.

• Inevitably, if installed horizontally, the performance of the 

   product will drop below 50 %.

• As shown in the figure, set the installation interval to a distance

   greater than the corresponding part size.

• Install the wiring duct at less than half the height of the heat 

   sink, so that it does not obstruct the flow of air.

• Since the SSR is satisfied under the ambient temperature of 25 ° C 

   or less, always use it in ambient temperatures lower than the

   standard temperature.

• When using 40A maximum load, use 10SQ wiring and use 

   clamping unit or lug when tightening.

• When installing the DIN rail, install it firmly because it is heavy.

• Since the load output terminal width is 13 mm and the input 

   terminal width is 7 mm, tightly tighten using a terminal that is less 

   than that. (Load side bolt: M5, control terminal: M3)

Vertical

Horizontal 

L1

13 mm

+C1

7 mm

Load terminal

Input signal terminal

Wiring duct

Wiring duct

Air out (FAN)

Air in

  Min.  60 mm

  Min.  100 mm

Min.  30 mm

   Min. 

 10 mm

INPUT

POWER

NC

NC

AL 80 ℃ (B)

+C1

-C2

+B1

-B2

BI AL (A)

AL COM

MADE IN KOREA

SSR-2B252Z

SOLID STATE RELAY

LOAD : 

90 - 264 VAC 25 A

INPUT : 

4 - 32 VDC 12 mA

INPUT

POWER

NC

NC

AL 80 ℃ (B)

+C1

-C2

+B1

-B2

BI AL (A)

AL COM

MADE IN KOREA

SSR-2B252Z

SOLID STATE RELAY

LOAD : 

90 - 264 VAC 25 A

INPUT : 

4 - 32 VDC 12 mA

INPUT

POWER

NC

NC

AL 80 ℃ (B)

+C1

-C2

+B1

-B2

BI AL (A)

AL COM

MADE IN KOREA

SSR-2B252Z

SOLID STATE RELAY

LOAD : 

90 - 264 VAC 25 A

INPUT : 

4 - 32 VDC 12 mA

INPUT

POWER

NC

NC

AL 80 ℃ (B)

+C1

-C2

+B1

-B2

BI AL (A)

AL COM

MADE IN KOREA

SSR-2B252Z

SOLID STATE RELAY

LOAD : 

90 - 264 VAC 25 A

INPUT : 

4 - 32 VDC 12 mA

28, Gilpa-ro 71beon-gil,  

Michuhol-gu, Incheon, Korea 

TEL : +82-32-876-4697 

http://www.hanyoungnux.com

HANYOUNGNUX CO.,LTD

2-Wire Break Alarm Output Solid State Relay 

SSR-2C

Thank you for purchasing Hanyoung Nux products. Please read the instruction 

manual carefully before using this product, and use the product correctly. 

Also, please keep this instruction manual where you can view it any time.  

MC1102KE210701

INSTRUCTION MANUAL

▍Safety information

   

DANGER

Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury

   

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury

   

CAUTION

Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or property damage

Please read the safety information carefully before the use, and use the product correctly.

The alerts declared in the manual are classified into 

Danger, Warning

 and 

Caution

 according to their importance

• The input/output terminals are subject to electric shock

   risk. Never let the input/output  terminals come in contact

   with  your body  or conductive substances.

DANGER

• Please make sure that the product specifications are the 

  same as you ordered. 

• Please use the product in places where corrosive gases

  (especially harmful gases, ammonia, etc.) and flammable 

   gases are not generated.

• Please use the product in places without liquids, oils, 

chemicals, steam, dust, salt, iron, etc. (pollution degree 1 or 2).

• Please avoid places where large inductive interference, 

  static electricity,magnetic noise are generated.

• Please avoid places with heat accumulation caused by 

   direct sunlight, radiant heat, etc.

• When water enters, short circuit or fire may occur, so 

   please inspect the product carefully.

• Do not connect anything to the unused terminals.

•  For DC types, please wire correctly, after checking the polarity

    of the terminals.  

• When disposing of the product, treat it as industrial waste.

• Pay attention to the edge of the heat sink, which may be sharp.

• The temperature of the main body and the heat sink may

   become extremely high when electric power is applied, 

   which may cause burns.

• In case of product malfunction, remove only the main body.

• Because the SSR heats up when power is on, the lower the

   heat sink and ambient temperatures, the longer the life.

• Please read the safety information carefully before the use, 

   and use the product correctly.

•  If there is a possibility that a malfunction or abnormality  of 

    this product may lead to a serious accident, install an 

    appropriate protection circuit on the outside and plan to 

    prevent accidents. 

•  Please supply the rated power voltage, in order to prevent 

    product breakdowns or malfunctions. 

• To prevent electric shocks and malfunctions, do not supply 

   power until the wiring is completed.

• Please disassemble the product after turning OFF the power. 

• Any use of the product other than those specified by the

  manufacturer may result in personal injury or property 

  damage.

• Please use this product after installing it to a panel, 

   because there is a risk of electric shock. 

WARNING

CAUTION

• If the heat sink temperature is lower than the  set 

  temperature  the alarm is automatically  released.

Voltage output of temperature 

controller, PLC, etc.

38.0

124.0

6.45

90.0

45.1

54.9

5.5

4.5

5.6

35.2

3.6

100.0

4.5

17.4

109.0

17.4

70.0

54.9

45.1

100.0

4.5

5.5

6.45

4.5

35.2

90.0

124.0

3.6

109.0

38.0

124.0

6.45

90.0

45.1

54.9

5.5

4.5

5.6

35.2

3.6

100.0

4.5

17.4

109.0

17.4

70.0

54.9

45.1

100.0

4.5

5.5

6.45

4.5

35.2

90.0

124.0

3.6

109.0

Reviews: