PARAMETER
DESCRIPTION
RANGE
DX
LEVEL
PRESS
TEMP
1u 00
Input signal type:
0 = input not active
1 = 0…10V or
0…20mA
2 = 4…20mA
3 = Temperature
0 – 3
2
2
2
3
1u 01
Signal display
minimum value
50…205
-30
0
0
-40°F
1u 02
Signal display
maximum value
50…205
+30
100
205
284°F
1u 04
Unit of universal input
(For analog inputs
only):
0 = no unit 1 = %
2 = °C/ °F
3 = PSIA
0 – 3
2
1
3
2
1u 05
Samples taken for
averaging control
signal
0...100
30
30
15
30
Fu 12
Remote Interlock
0 = disable
2 = enable
0 or 2
2
2
2
2
1L 27
Startup Delay
0-255
2
0
0
0
1L 11
P – band reverse
acting XPH
Acc Input
10.0°F
10.0%
10.0PSIa
10.0°F
1L 12
P – band direct acting
XPC
Acc Input
10.0°F
10.0%
10.0PSIa
10.0°F
1L 13
KIH, Integral gain
reverse acting, in 0.1
steps
low value =
slow reaction
high value =
fast reaction
0…25.5
8.0
0.1
0.1
0.1
1L 14
KIC, Integral direct
acting, in 0.1 steps
0…25.5
8.0
0.1
0.1
0.1
1L 15
TI, measuring interval
integral
low value =
fast reaction
high value =
slow reaction
0…255 sec
30
15
15
30
6
PXVC
AUGUST 2018
PXVC UNIVERSAL CONTROLER
Note: Hansen controller is factory programmed to provide precise control in refrigeration applications when used in conjunction with
the PXV valve or Hansen Motorized Control Valves. If control difficulties occur during startup, it is recommended to thoroughly check
system and components for proper installation, operation, and sensor location before attempting to modify and/or tune the controller.
Hansen controller is a multi-use controller and only the listed parameters should be accessed/changed. Any other parameter changes
may result in unsafe operation. Consult factory for further details if needed.
PARAMETER ACCESS CODE 0241
TABLE 1.