background image

6

A100g 
JULY 2017

*ADD 3.25” (83) FOR SHIELD

WIRING GAS SENSORS 

Install the Hansen Gas Sensor in an area where operating 
personnel can easily monitor the remote sensor. Refer 
to 

Gas Sensor Location

 on page 3 for suggestions on 

proper placement of Remote Sensors.

Use three-wire (VDC supply voltage), twisted pair shielded 
cable such as Belden 8770 or equivalent to connect 
the gas sensor to the gas monitor (page 15), GAS Alert 
System (page 19), customer supplied PLC or computer 
(page 20). When powering the gas sensor from a VAC 
power supply use four-wire, twisted pair shielded cable, 
such as Belden 82418 or equivalent. Connect the power 
input wires to terminals ØV and +V. Set applied voltage 
jumper to appropriate AC or DC position. Extreme Gas 
Sensor requires an additional external 24V AC or DC 
power supply wired with 18 AWG cable. Refer to Fig. 21 
for wiring details. Connect the signal wire to terminal I 
for 4-20mA output or V terminal for 1-5 volt output. The 
4-20mA output is best for long distances to the monitor 
and where electrical noise is a problem. The voltage output 
is for short distances within 10 feet (3 m) of the monitor. 
The maximum 4-20mA cable length is 1000 ft (300 m).

Under no circumstances should the gas sensor low 
voltage signal wires be in a common conduit, tray or 
wiring panel with power wiring over 48 volts. Do not run 
wires near variable frequency drive (VFD) equipment.  
When using the gas sensors connected directly to a 
customer supplied PLC or computer, refer to Fig. 20 
for wiring details.

Hansen recommends backup of gas detection system 
with an uninterruptable power supply to provide battery 
backup in the event of a power failure.

INSTALLATION

Mounting the gas sensor varies by model. Refer 
to 

Installation Dimensions

 below for mounting 

requirements.

SENSING ELEMENT

Typical sensor life is based on normal operating 
conditions. Exposure to the target gas will shorten these 
times. The typical sensor life of the electrochemical gas 
sensor element is 1 to 2 years; typical sensor life for 
semiconductor element is 2 years; and typical sensor 
life for infrared element is 5 to 7 years. Recalibration 
should be performed at least every 6 months. Calibration 
can be performed locally at sensor installation site. If 
desired results cannot be achieved or if signal reads 
0.5mA, replacement of the sensor element may be 
required. See 

Sensor Element Replacement

 section 

for further instruction.

Note: Insurance companies, local and state agencies 
may require more frequent testing and calibration; refer 
to insurance carrier mandates as well as local and state 
codes.

INSTALLATION DIMENSIONS

INCHES (MM)

FIG. 8

BASIC

STANDARD & HARSH

EXTREME

EXPLOSION PROOF

Summary of Contents for HSC4H-N10K

Page 1: ...urrounding environment The analog outputs 4 20mA or 0 10V DC can interface with nearly any existing monitor computer or PLC controller The sensing elements except Basic and Extreme Gas Sensors are mou...

Page 2: ...ors or outdoors Enclosure is NEMA4X IP65 conduit connection must be vaporproof Note Auxilliary power required when used with Hansen monitors HLM2 and HLM6 and Gas Alert System Vent Line Gas Sensor For...

Page 3: ...mount the gas sensor below the coil to avoid high moisture and steam during defrost The two generally accepted methods of locating sensors are Point and Perimeter detection Point detection is where se...

Page 4: ...LOOP RESISTANCE 1000 OHMS OUTPUT 4 20mA 0 5V 1 5V 0 10V 2 10V DC 4 20mA SIGNAL OUTPUT Isolated 2 wire ALARM RELAY SPDT 1 A 120V TRUE ALTITUDE 2000M POLLUTION DEGREE 2 4 EQUIPMENT CLASS 3 INSTALLATION...

Page 5: ...ALARM SIMPLE ALARM SYSTEM INDOOR OUTDOOR VISUAL ALARM AUDIBLE ALARM GAS SENSOR INSIDE SPACE OUTSIDE SPACE GAS SENSOR ELEMENT 10 3m CABLE MAX WEATHER PROOF GAS SENSOR ELECTRONICS RELIEF LINE DISCHARGE...

Page 6: ...tage signal wires be in a common conduit tray or wiring panel with power wiring over 48 volts Do not run wires near variable frequency drive VFD equipment When using the gas sensors connected directly...

Page 7: ...SHIELD AT OTHER END Voltage Selector D 24V DC A 24V AC D A Fail Safe Relay Relay engerized to normally open position when power applied AC APPLIED VOLTAGE POWER SEMI CONDUCTOR SENSOR NO NC COM V V 0 V...

Page 8: ...8 A100g JULY 2017 INFRARED SENSOR SHOWN WIRED FOR 4 20MA OUTPUT FIG 11...

Page 9: ...SOR OPERATION On power up the internal relay will energize switching from the normally closed position to the normally open position In addition the sensor will go through an initial warm up delay for...

Page 10: ...e output it should begin to increase after 5 seconds Leave the gas flow on and observe the voltage The sensor voltage will slowly climb toward 5VDC When the voltage does not change by more than 0 010...

Page 11: ...oof Sensing Elements are externally mounted to the enclosure To replace disconnect power open enclosure and disconnect cable wire from the circuit board Unscrew sensor element from enclosure Install n...

Page 12: ...relays alarms 10 amp 230V AC 1 SPDT dry contact relay fault output 10 amp 230V AC HLM6 Model only Power Required 100 230 VAC Power Consumption HLM2 15W HLM6 25W Audible Alarm HLM2 internal 80 dB HLM6...

Page 13: ...ge across VHIGH and GND Set the desired high level alarm relay using VHIGH Pot which is located furthest from the calibration pins This setting applies to the six channels SETTING ALARM OUTPUT FOR HLM...

Page 14: ...14 A100g JULY 2017 HLM2 WIRING DIAGRAM FIG 13...

Page 15: ...15 A100g JULY 2017 HLM6 WIRING DIAGRAM FIG 14...

Page 16: ...m sensor fault Symptom Output from sensor is 2mA for 4 20mA output Output from sensor is 0 V or 5V for 0 10 0 5 1 10 1 5 output signals Cause 1 Sensing element has failed or is disconnected from print...

Page 17: ...6 5 94 151 2 56 65 62 16 2 07 53 4 13 105 173 DIA 4 4 MOUNTING HOLE 3 PLACES 29 7 2 93 78 6 37 162 358 DIA 9 1 MOUNTING HOLE 3 10 79 7 58 191 173 DIA 4 4 MOUNTING HOLE 3 PLACES 358 DIA 9 1 MOUNTING HO...

Page 18: ...monitored system or as part of a larger gas monitoring and signaling system The lower cover to the terminal compartment must be removed to gain access for wiring Knockouts are available for and condui...

Page 19: ...REEN RED REMOTE SENSOR V V V I NO COM NC 0 0 V V V I COM CONTROL 0 RELAY NC RELAY COM SIGNAL POWER COM SHIELD SIGNAL POWER POWER SHIELD ppm Power Supply 24V AC DC EARTH GRD Multi Wire Cable Shield JUM...

Page 20: ...4 PT ANALOG IN MODULE CURRENT GREEN RED V V V I NO COM NC 0 0 V Power Supply 24V AC DC EARTH GRD Multi Wire Cable Shield REMOTE SENSOR INPUT 1 INPUT 2 INPUT 3 INPUT 4 ANALOG GND REMOTE SENSOR REMOTE...

Page 21: ...21 A100g JULY 2017 TYPICAL WIRING DIAGRAM WITH LOCAL POWER SOURCE FIG 22...

Page 22: ...nnected to relay _______________________________ OK Check Analog Output in Use e g 0 5V 4 20 mA _______________________________ OK 2 On Site Gas Calibration Initial the following encircle OK when comp...

Page 23: ...4E F3K R410 Semiconductor 0 3 000 Note Gas Sensors available for additional refrigerants consult factory TABLE 9 CO2 Sensor Type Range PPM Basic to 32 F 0 C Harsh to 40 F 40 C Extreme to 60 F 50 C HIR...

Page 24: ...conductor 31 1025 Harsh Extreme Ammonia 100 250 Electrochemical 31 1005 Harsh Extreme Ammonia 1000 Electrochemical 31 1006 Harsh Extreme Ammonia 10 000 Semiconductor 31 1007 Vent Line Ammonia 10 000 S...

Reviews: