![Hans Turck BL20-E-GW-CO Instructions For Use Manual Download Page 46](http://html.mh-extra.com/html/hans-turck/bl20-e-gw-co/bl20-e-gw-co_instructions-for-use-manual_594297046.webp)
Guidelines for Electrical Installation
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
44
8.3.7
EMC compliant cabinet installation
A
Bonding straps
Bonding straps connect inactive metal components, if it is not possible to create a large surface area contact. Use
short bonding straps with large surface areas.
B
Mounting plates
Mounting plates used to hold control components must have a large surface area contact with the cabinet hous
-
ing.
C
Protective conductor rail
The protective conductor rail must also be connected over a large surface area to the mounting plates and addi
-
tionally with an external cable (cross-section at least 10 mm2/0,015 inch2) to the protective conductor system to
avoid interference currents.
D
Protective conductor terminal block
The protective conductor terminal block must be connected to the protective conductor rail.
E
Protective conductor system cable (grounding point)
The cable must be connected over a large surface area with the protective conductor system.
EMC compliant cabinet installation