HAMWORTHY HEATING LTD
24
SHERBORNE
500001167/E
8.6.4 - FUNCTIONS
8.6.4.1 - Chimney Sweep mode
This mode is intended for use when making measurements on the boiler. When the chimney sweep mode is
activated, the boiler will deliver maximum output until the limit thermostat cuts out.
This mode is enabled by pressing both buttons for between 3-6 seconds.
On the display, the upper arrow of the
maintenance symbol flashes & the currently selected temperature appears.
To leave this mode press the mode button.
8.6.4.2 - Controller Stop mode
The controller stop mode enables the boiler’s heat output to be adjusted manually in heating mode by pressing
both buttons simultaneously for more than 6 seconds.
On the display, the lower arrow of the maintenance symbol flashes & the currently selected temperature appears
& the display shows the adjusted relative boiler output.
Minimum & maximum output can be directly selected by pressing the arrow buttons
To leave this mode press the mode button
8.6.4.3 - Time of day function
To ensure that this function operates, the time of day & time settings must be correctly set. Refer to section 8.3.2
for an explanation of how to set this.
Each time the + or - button is pressed during the time setting, the seconds are set to 0. The clock continues to
run while making the setting.
To leave this mode press the mode button
8.7.10 - Display of operating phases
The operating phases according to the controls sequence diagram can be displayed. Assignment of the display
code & the LMU...’s phase designation is as follows:
Note:
-If operating phases are passed very quickly or skipped, the relevant display code will not appear.
Display Meaning
Internal
Operating Phases of the LMU ….
00
Standby (no demand for heat)
PH STANDBY
01
Prevention of startup
PH_STARTVER
02
Fan runup
PH_THL_1 & PH_THL1_2
03 Pre-purging
PH_TV
04
Waiting time
PH_TBRE, PH_TW1 & PH_TW2
05 Pre-ignition
time
PH_TVZ
06
Safety time, constant
PH_TSA1 & PH_TSA2_1
07
Safety time, variable
PH_TSA1_2 & PH_TSA2_2
10
Heating operation
PH_TI, PH_MODULATION & Heating mode
11
DHW operation
PH_TI, PH_MODULATION & DHW mode
12
Parallel operation of space heating & DHW operation
PH_TI, PH MODULATION, Htg & DHW MODE
20
Post-purging with last control of operation
PH_THL2_1 & PH_TN_1
21
Post-purging with control of pre-purging
PH_THL2_2 & PH_TN_2
22
Home run
PH_TNB, PH_TLO & PH_TNN
99
Lockout position (display of the current error code)
PH_STOER
Summary of Contents for Sherborne SE64he
Page 2: ......
Page 10: ...HAMWORTHY HEATING LTD 8 SHERBORNE 500001167 E 4 Boiler Layout Description 4 1 Accessory Pack...
Page 27: ...HAMWORTHY HEATING LTD 25 SHERBORNE 500001167 E...
Page 29: ...HAMWORTHY HEATING LTD 27 SHERBORNE 500001167 E 8 9 Wiring Diagram...
Page 30: ...HAMWORTHY HEATING LTD 28 SHERBORNE 500001167 E 8 10 Wiring Diagram LMU...
Page 53: ......
Page 54: ......