Figure 8.6.4 Master control blocking errors (E) - auto reset
Display Nr PC Nr
Fault
Action
E02
51
Flow temperature sensor T1 - open circuit
Check and replace mixed flow sensor T1
E04
53
DHW temperature sensor T3 - open circuit
Check and replace DHW sensor T3
E18
67
Flow temperature sensor T1 - short circuit
Check and replace mixed flow sensor T1
E20
69
DHW temperature sensor T3 - short circuit
Check and replace DHW sensor T3
E23
28
Internal temperature calibration error
Check and replace Master board
E24
29
Internal temperature calibration error
Check and replace Master board
E25
0
Internal E2PROM error
Check and replace Master board
E25
30
Internal temperature calibration error
Check and replace Master board
E26
31
Internal temperature calibration error
Check and replace Master board
E32
33
No slaves connected
Check the position of the Bi-Polar switches.
Check the slave addresses
Check slave electrical connections
Check and replace Master board
Check and replace Slave board
E34
42
Supply frequency error
Main frequency is not 50Hz
Figure 8.6.5 Boiler module permanent lock-out errors (A) - manual reset
A01
1
5 failed attempts of starting up
Check the gas cock
Check for spark and condition of ht. lead
Check and replace Slave board
A02
2
Too many failed ignition attempts
Check and clean or replace the spark elec-
trode.
Check and clean or replace the ht lead.
A04
4
Intervention of limit stat > 90°C
Check and correct boiler flow rate
Check and replace limit thermostat
A05
5
Failed gas valve
Faulty connection on gas valve lead
Check and replace the gas valve
Check and replace the gas valve cable
A06
6
Internal error
Check and replace Slave board
A07
7
Internal error
Check and replace Slave board
A08
8
Internal error
Check and replace Slave board
A09
9
Supply frequency error
Main frequency is not 50Hz
A10
10
Internal error
Check and replace Slave board
A11
11
Internal error
Reset, check and replace Slave board
A12
12
Internal error
Check and replace Slave board
A16
16
Intervention of limit stat > 90°C
Check and correct primary flow rate
Check and replace limit thermostat
A19
19
Flue sensor error (fan will run at max. speed)
Check and clean heat exchanger
Check and replace flue sensor
A20
20
Flame detected after closing the gas valve
Check and replace the gas valve
A22
22
Internal error
Check and replace Slave board
A24
24
Fan error - speed not achieved
Check the fan and electrical connections.
Replace the fan