APPENDIX A - GAS DATA
GENERAL DATA
BOILER MODEL
F175V-350 F175V-525 F200V-400 F200-V600
Boiler Input (maximum)
- kW (Gross)
359.7
539.5
411.1
616.6
Boiler Input (maximum)
- kW (Nett)
324.1
486.1
370.4
555.6
Boiler Output (maximum) condensing 50/30°C
- kW
350
525
400
600
Boiler Output (maximum) non condensing 80/60°C - kW 316.6 474.9
361.8 542.7
Boiler Module Output (minimum) 80/60°C
-
kW 31.7
31.7
36.2
36.2
Boiler Module Output (minimum) 50/30°C
-
kW 35.0
35.0
40.0
40.0
F250V-500 F250V-750 F300V-600 F300V-900
Boiler Input (maximum)
- kW (Gross)
513.8
770.7
616.6
924.9
Boiler Input (maximum)
- kW (Nett)
462.8
694.2
555.6
833.4
Boiler Output (maximum) condensing 50/30°C
- kW
500
750
600
900
Boiler Module Output (minimum) 80/60°C
-
kW 45.2
45.2
54.3
54.3
Boiler Output (maximum) non condensing 80/60°C - kW 452.4 678.6
542.7 814.2
Boiler Module Output (minimum) 50/30°C
-
kW 50.0
50.0
60.0
60.0
F350V-700 F350V-1050
Boiler Input (maximum)
- kW (Gross)
719.3
1079.0
Boiler Input (maximum)
- kW (Nett)
648.2
972.3
Boiler Output (maximum) condensing 50/30°C
- kW
700
1050
Boiler Output (maximum) non condensing 80/60°C - kW 633.2 949.8
Boiler Module Output (minimum) 80/60°C
- kW
63.3 63.3
Boiler Module Output (minimum) 50/30°C
- kW
70.0 70.0
Figure A1– Gas data
F300V
F350V
Gas Inlet Connection Pipe Thread Size
R 1¼”
R 1¼”
Nominal Inlet Pressure Nat Gas
-mbar
20
Maximum Inlet Pressure Nat Gas
-mbar
25
Gas Pressure Switch Setting Nat Gas
-mbar
12.5
Gas Flow Rate (max. per module) Nat Gas -m
3
/h
29.3
34.2
Target CO
2
% at High / Low fire Nat Gas ±0.25%
9.2 / 10.0
GAS DATA - per boiler module
F175V
F200V
F250V
Gas Inlet Connection Pipe Thread Size
R 1”
R 1”
R 1”
Nominal Inlet Pressure Nat Gas
-mbar
20
Maximum Inlet Pressure Nat Gas
-mbar
25
Gas Pressure Switch Setting Nat Gas
-mbar
12.5
Gas Flow Rate (max. per module) Nat Gas -m
3
/h
17.1
21.7
24.4
Target CO
2
% at High / Low fire Nat Gas ±0.25%
9.2 / 10.0