6
Hampton H35 Direct Vent Freestanding Gas Stove
INSTALLATION
4)
This appliance is Listed for bedroom instal-
lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
5)
This appliance is Listed for Alcove installa-
tions, maintain minimum Alcove clearances
as follows, minimum width of 40" (1016mm),
a maximum depth of 36" (914mm), and
minimum ceiling height of 64" (1626mm)
from floor to ceiling.
6)
We recommend that you plan your installa-
tion on paper using exact measurements
for clearances and floor protection before
actually installing this appliance. Have a
qualified building inspector review your
plans before installation.
GENERAL SAFETY
INFORMATION
1)
The appliance installation must conform
with local Canadian Electrical Code.
2)
The appliance when installed, must be elec-
trically grounded in accordance with local
codes, or in the absence of local codes with
the current National Electrical Code, ANSI/
NFPA 70 or CSA C22.1 Canadian Electrical
Code.
3)
The appliance should be inspected for
shipping damage before use and
serviced
annually by a professional service per-
son
. More frequent cleaning may be re-
quired due to excessive lint from carpeting,
bedding material, etc. It is imperative that
control compartments, and circulating air
passageways of the appliance be kept
clean and free from excessive lint from
carpeting.
4)
See general construction and assembly
instructions. The appliance and vent should
be enclosed when installed in or passing
through a living area, where children may
come in contact with it.
5)
This appliance must be connected to the
specified vent and termination cap to the
outside of the building envelope.
N e v -
er vent to another room or inside a building.
Make sure that the vent is fitted as per the
instructions starting on page 9.
6)
Inspect the venting system annually for
blockage and any signs of deterioration.
7)
Venting terminals shall not be recessed into
a wall or siding.
8)
Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
9)
To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.
INSTALLATION
CHECKLIST
1)
Check Clearances to Combustibles (page
6), location of unit (page 7) and venting
requirements (pages 8-15).
2)
Install Optional Fan, see page 7.
3)
Set vent restrictors, page 8.
4)
Install venting: Check all venting require-
ments, pages 8-15. Vertical Termination
with Co-linear Flex System, page 16. Hor-
izontal Termination Kits , page 17. Dura-
Vent Termination Kits, page 19.
5)
Make gas connections, page 24. Test the
pilot. Must be as per diagram, page 35.
If converting to Propane, make changes
prior see pages 25.
6)
Test Gas Pressure, page 25.
7)
Install logs and embers where indicated on
page 28.
8)
Install optional Remote Control, or Wall Ther-
mostat, page 32.
9)
Final check, page 33.
Before leaving this unit with the customer, the
installer must ensure that the appliance is firing
correctly and
operation fully explained to
customer
.
This includes:
1)
Clocking the appliance to ensure the cor-
rect firing rate (rate noted on label) after
burning appliance for 15 minutes.
2)
If required, adjusting the primary air to
ensure that the flame does not carbon. First
allow the unit to burn for 15-20 min. to
stabilize.
CAUTION: Any alteration to the product
that causes sooting or carboning that
results in damage is not the responsibil-
ity of the manufacturer.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance
and the chimney connector.
The farthest
distance is correct if the two clearances
do not coincide.
For example, if the appliance is set as indicated
in one of the figures but the connector is too
close, move the stove until the correct clear-
ance to the connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one
type of installation with another in order
to achieve closer clearances.
This unit can be installed on a solid combustible
surface like a wood floor. This unit can also be
installed directly on carpeting or vinyl.
Use the minimum clearances shown in the
diagrams below:
H35-NG & H35-LP Clearances
A Side Wall to Unit
6-1/2" / 165 mm
B Back Wall to Unit
6" / 152 mm
C Vertical Vent Pipe to Back Wall
2" / 50 mm
E Unit Corner to Wall
2" /50 mm
Unit Top to Alcove Ceiling 36" / 914 mm
Minimum ceiling height is 36" /914 mm from top
of unit.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.