The condensate trap and entire drain system attached to it (above the neutralizer) should be cleaned at 
least once every year.

 

 

1) Turn off the power to the EVO.

 

 

2) Place a bucket under the condensate trap. Use caution when removing the clean-out cap, as 

 

 

    the trap is full of condensate and it may be hot.

 
  

 

 

3) Remove the condensate clean-out cap, and be sure the

 

 

    bucket is under the open drain trap assembly to catch

 

 

    the debris and water. 

                    

 

 

 

4) Rinse out the clean-out cap in a sink to remove any dirt or buildup that may have accumulated.                    

 

 

 

5) Condensate drain assembly should now be checked for non-restricted flow throughout the 

 

 

    entire assembly.

 

 

    

  

  

 

 

6) Reinstall the clean-out cap on the condensate trap.

 

 

7) Turn on the power to the EVO.

 

 

8) Make sure the hose from the condensate trap is not submerged too far into the neutralizer, 

 

 

    there should be an air gap between the highest level of condensate and the outlet hose from the trap.

 

 

9) Monitor the condensate drain until flow has been established.

CONDENSATE TRAP CLEANING INSTRUCTIONS

Summary of Contents for EVO 129

Page 1: ...ld result in loss of warranty and or severe personal injury death and or substantial property damage 34000 Autry Street Livonia MI 48150 800 968 5530 Fax 734 419 0209 www hamiltonengineering com LIT91...

Page 2: ...the owner An inspection should cover at a minimum the following areas Download and review operating hour data and fault history Inspect all fittings controls and connections for leaks damage or fouli...

Page 3: ...e front of the heat exchanger to break If excess resistance is encountered when installing a M6 nut discard that nut and use one of the spares shipped with the unit The maximum torque for assembling a...

Page 4: ...te cleaning instructions on page 53 55 Check the distance from the electrode to the burner there should be a 3 8 gap in between the two If the existing electrode pins must be adjusted for proper gap c...

Page 5: ...PRESSURE P MODEL AIR PRESSURE P HW129 6 wc HW399 1 wc HW179 96 wc HW599 86 wc HW199 1 68 wc HWH 1499 1999 8 wc Hamilton EVO Products Flow and Pressure Drop GPM Feet of Head Design HW 79 129 8 HW 179 1...

Page 6: ...at high fire Water temperature 160 180 F gives the hottest flue gasses All readings must be taken with boiler front cover installed Doing the measurements under these conditions will give the most acc...

Page 7: ...e sure the bucket is under the open drain trap assembly to catch the debris and water 4 Rinse out the clean out cap in a sink to remove any dirt or buildup that may have accumulated 5 Condensate drain...

Page 8: ...t and should always be replaced during the annual maintenance procedure To limit risks the following instructions must be adhered to PROPER PROCEDURE Before installing a burner door the two gaskets an...

Page 9: ...ering com LIT91178 REV 5 2017 Page 9 of 9 INSTALLATION OF THE BURNER DOOR DURING SERVICING New Burner Door Rope gasket in good condition Rope gasket raised above door surface good Damaged Burner Door...

Reviews: