Halton EcoloAir 10000CFM Installation Manual Download Page 2

2

EcoloAir Installation Manual

 

EA

OMSI/0620

09/re

v1/EN

FIGURE 1

FIELD CONNECTION OF FILTER AND FAN MODULES

FILTER HOUSING

FAN HOUSING

TOP ELEVATION

BOTTOM ELEVATION

BLANK SIDE INSULATED LINING

AND SKIN (STANDARD)

BLANK SIDE (INTERIOR INSULATION 

LINING) AND SKIN OPTIONAL

CONNECTION FLANGE 

INTERIOR AND BLANK SIDE

INTERIOR BOTTOM FLOOR

CONNECTION OUTLET END

FILTER ACCESS SIDE

REMOVE TO GAIN ACCESS TO 

BOTTOM FLANGE CONNECTION

FILTER OUTLET END MULLION

WITH CONNECTION FLANGE

SEE NOTE FOR 

METHOD OF CONNECTIONS

INTERIOR BOTTOM FLOOR

PANEL TURNED UP AT

FAN INLET

GASKET TO BE PLACED

BETWEEN FLANGES

FILTER TOP INSULTATION LINING

(STANDARD 1)

INTERIOR FILTER TOP PANEL

INTERIOR CONNECTION DETAIL

LOCATED @ TOP OF FILTER

OUTLET IF AN INLET

B FAN TOP INSULATION LINING

(OPTION FOR EXTERIOR ICN)

INTERIOR FAN 

TOP PANEL

BOTTOM FLOOR PANEL 

WITH TURNED UP FLANGE 

AT FAN INLET

INTERIOR FLOOR CONNECTION

FLANGE FILTER OUTLET

4” STRUCTURAL FLOOR BASE

PLAN VIEW

INLET PANEL

CONNECTION

FLANGE

ACCESS SIDE

INLET GASKET

(PROVIDED BY

 FACTORY)

FAN BOTTOM

PANEL

TURNED UP 

FLANGE

FAN TOP PANEL

(LESS INSULATION)

FILTER BLANK

SIDE CONNECTION

BY CONTRACTOR

FILTER TOP

CONNECTION POINTS

FILTER TOP

INSULATION SKIN

DRILLING OF HOLES

FOR BOLTED CONNECTIONS OR

USE OF SELF TAPPING SCREWS

BY CONTRACTOR. 1/4” - 20 ON 6” 

CENTERS TYP. GASKETED WITH 

SILICONE TAPE. 

FILTER FLOOR PANEL

FILTER FLANGE ACCESS SIDE

CONNECTION POINT

FIGURE 1A

DRAWING FOR: FILTER MODULE TO FAN SECTION OR 
                            FILTER MODULE TO ODOR CONTROL TO FAN SECTION  

NOTE:

 BASED ON THE SIZE OF 

THE UNIT, THE CONNECTING 

FLANGES COULD BE INTERNAL 

OR EXTERNAL.

Summary of Contents for EcoloAir 10000CFM

Page 1: ...URE ELECTRICAL SUPPLY CONFORMS WITH ELECTRICAL CHARACTERISTICS SHOWN ON THE RATING PLATE AND N E C REQUIREMENTS THE INSTALLATION OF THE HOOD AND DUCT WORK LEADING TO AND EXITING THE ECOLOAIR SYSTEM TO BE INSTALLED IN ACCORDANCE WITH NFPA 96 AND LOCAL CODES UL 1978 Standard for Grease Ducts UL 710 Exhaust Hoods for Commercial Cooking Equipment ULC S647 05 and or UL197 ...

Page 2: ... DETAIL LOCATED TOP OF FILTER OUTLET IF AN INLET B FAN TOP INSULATION LINING OPTION FOR EXTERIOR ICN INTERIOR FAN TOP PANEL BOTTOM FLOOR PANEL WITH TURNED UP FLANGE AT FAN INLET INTERIOR FLOOR CONNECTION FLANGE FILTER OUTLET 4 STRUCTURAL FLOOR BASE PLAN VIEW INLET PANEL CONNECTION FLANGE ACCESS SIDE INLET GASKET PROVIDED BY FACTORY FAN BOTTOM PANEL TURNED UP FLANGE FAN TOP PANEL LESS INSULATION FI...

Page 3: ...CT CONNECTIONS 1 The exhaust duct connection at the inlet entrance to the EcoloAir system must be continuously welded all around See figure 2 2 The duct must be transitioned to the full opening of the filter module inlet 3 All fan outlet openings to which ducts are attached will be provided with discharge collars See figure 3 4 All openings are to be transitioned to the duct size 5 For filter modu...

Page 4: ... the filters be properly seated against the support mullion as shown in figure 4 and 5 ECOLOAIR UNIT FILTER SUPPORTING FRAME PRE FILTER MERV 7 AIR FLOW EXHAUST FILTER INLET MEDIUM FILTER MERV 14 FIGURE 4 FILTER AIR SEAL GASKETING CLAMP HANDLE TAPED TO SIDE OF FILTER FOR SHIPPING ABSOLUTE FILTER MERV 16 FILTER CLAMP PULL OUT TO LOOSEN FILTER PUSH IN TO TIGHTEN FILTER AGAINST AIR SEAL CENTRE MULLION...

Page 5: ...d installed SCHEMATIC WIRING DIAGRAMS For field wiring diagrams and field connections refer to Halton s shop drawings shipped with unit or contact factory Additional copies of shop drawings are available on request FAN SECTION Important note Before starting the fan unit remove fan isolator hold down brackets The brackets are used for shipping purposes only When the brackets are removed the fan sho...

Page 6: ...ce charges miscellaneous tools material charges and labor charges resulting from inaccessibility of equipment will not be paid by Manufacturer This LIMITED WARRANTY SHALL APPLY ONLY to products that have been installed and maintained in accordance with the installation and Care Instruction Manuals Purchaser shall be solely responsible for adhering to the instructions and procedures set forth in th...

Reviews: