CONTROL PANEL OPERATION
The UV control panel is designed to operate the UV lamps only under safe conditions and warn when
there are lamp failures, fan failures, the lifetime of the lamps has been exceeded or other operational
failures. If these solutions do not fix the problem, refer to the Troubleshooting Guide later in this
manual.
If an alarm goes off on the panel it indicates then there is a problem with the UV operation. To silence
the alarm, press the “MUTE” button; however, the indicator lamps will remain lit. To reset the 10,000
hour clock, it is necessary to use the keypad to reset the timer.
DISPLAY
CAUSE
SOLUTION
Error
A lamp has failed, the voltage to
the lamp is too low, or the lamp
ballast has failed.
- Check line voltage
- Replace UV Lamp
- Replace lamp ballast if needed
No Fan
Either the fan is at a lower speed
or belt has broken
Either a KSA filter is not in place
in the hood or the cassette
access door is open.
- Examine and tighten or replace
fan belt if needed.
- Replace fan if needed.
- Check that all filters are
installed and the cassette
access door is closed and
fastened.
10,000 Hour Maintenance
The expected lifetime of the
lamps have been reached.
- Replace the UV lamps. Failure
to do this will cause the
system to not be efficient.
Fire
The fire system has been
activated.
STANDARD CONTROL PANEL
4"
12"
10 "