7100.006194 PS17 Assembly instructions
PS 17 Differential pressure transmitter
The PS17 is a stationary differential pressure transmitter used
for recording positive and negative differential pressures and
converting them into electrical signals.
The device is designed for use in cleanrooms, machines, filter
technology and heating, ventilation and air-conditioning systems
(HVAC). It is used to measure the differential pressure of non-
aggressive and non-combustible gases up to 10 kPa.
The device may only be used in the allowed measuring range
(see type label).
Symmetrical and asymmetrical measurement ranges can be
measured with the piezoresistive pressure transmitter.
Models
The device is available in different models:
-
With one fixed measurement range or
toggling between 4 different measurement ranges
-
3 supply connection options:
a. 24 VAC / DC (with reverse polarity protection)
b. 15.. 32 VDC (2-wire)
c. 24 VDC (with galvanic separation)
-
3 electrical connection options:
a. 2 cable glands M16
b. 1 cable gland M20 (not for version with relay)
c. 1 connector M12 (not for version with relay)
-
Optional with 3 ½-digit display
-
Optional with contact point/relay (not for 2-wire, cable gland
M20 or connector M12)
The time constant and output signal are default settings (see
type label). However, these settings can be configured.
Configure settings
The device has numerous possible settings:
-
Adjustment of time constant
-
Zero-point calibration of measured values
-
Fine adjustment of final value
-
Restore factory settings
-
Configure output signal
-
Adjust measuring range (optional)
-
Set relay/switching threshold (optional)
To adjust these functions, please use the detailed operating
instructions at:
www.halstrup-walcher.de/technischedoku
Control units and dimensions of the device
1.
Display (optional)
2.
Mounting option
-
Wall mounting with 2 screws
-
Top-hat rail mounting
3.
Electrical connection option
-
2 cable glands M16
-
1 cable gland M20
-
1 connector M12
4.
Hose connections 4 or 6 mm
5.
Flap for opening the housing
6.
Type label
a.
Version without display
b.
Version with display
Safety precautions
These assembly instructions are part of the product. Please read
the instructions carefully, follow our handling instructions and
pay particular attention to the safety precautions. The
instructions should be on hand at all times. Please contact the
manufacturer if you do not understand any parts of these
instructions.
The device has been designed and tested to ensure its safety.
However, it may still be dangerous if used inappropriately.
Always observe the operating requirements indicated on the
type label and in the data sheet
– particularly the permissible
supply voltage.
Installation may only be carried out by qualified personnel. The
device requires no maintenance. The device may only be
cleaned from the outside with a damp cloth. The individual
responsible for the electrical connections must be notified
immediately if the device is damaged. In the event of
malfunctions, please consult the detailed operating instructions
at:
www.halstrup-walcher.de/technicaldocu
Repairs should only be carried out by the manufacturer.
WARNING
Inside the device there may be electrical conductors with a
voltage of 230 V (relay option).
The device must be disconnected from the power supply
and secured before opening!
The device may only be opened and connected to an
electrical power source by qualified personnel.
1
2
3
4
5
6a
6b