MAN3184 - TITANUS PRO
•
SENS®
38
Figure 31:
Condensate separator type KA-1
Automatic condensate separation is possible due to a capillary effect thanks
to an integrated cotton wick. The condensate separator can be operated
within a temperature range of 0 °C … +60 °C.
3.3.9 Detonation prevention device
Figure 32:
Detonation protector
Due to the additional installation of detonation protectors in the pipe system,
the TITANUS PRO·SENS® can also be used for monitored areas with
potentially explosive atmospheres (Ex areas). Detonation protectors are
used as protection in Ex areas, as pipe deflagrations or detonations can
occur in the event of ignition of vapour/air mixtures or gas/air mixtures. This
depends on the type and concentration of the ignitable mixture, the initial
pressure and temperature. The TITANUS PRO·SENS® as well as the
detonation protectors must be installed outside of the Ex area.