MAN3184 - TITANUS PRO
•
SENS®
168
9.5 Replacing the detector module
Figure 103:
Replacing the detector module
Only perform the following work with the device disconnected from the
mains.
► Carefully unlock the clips on the housing using a flat-head screwdriver
by simultaneously pressing in the closing flaps on one side. Then
carefully lift the housing cover.
► Pull the display circuit board cable from the basic board and remove the
housing cover.
► Remove the detector module connection cable from the basic board.
► Carefully spread the two retaining clips on the detector module apart
and take the module out.
► Transfer the settings of the old detector module onto the new detector
module.
Only type DM-TP-xx detector modules (yellow rating plate) may be used.
ATTENTION