MAN3184 - TITANUS PRO
•
SENS®
160
Checking the fault signal
transmission
▪ …any test adapters and air filters are connected.
▪ …any filter inserts are clean.
▪ …any ball valves and clearing valves are in "operating position".
If no defects are established, the TITANUS PRO·SENS® or airflow sensor is
checked for functionality using a test pipe or diagnostic software (see section
"Function test").
► Check the fault signal transmission.
8.4 Function test
If the TITANUS PRO·SENS® cannot be calibrated, check its functionality
using the test pipe and a digital pressure gauge or the diagnostic software.
The TITANUS PRO·SENS® must be in operation for at least 30 min.
8.4.1 Function test preparations
The following steps can only be carried out after airflow calibration is
completed in accordance with section "Airflow sensor calibration".
NOTICE
For a TITANUS PRO·SENS® with 2 pipe systems, preparation for the
function test must be carried out with work steps 1 to 4 for both pipe
systems.
NOTICE