71-0149 Hallmark 46 57 SL2 Manual
Date: 12/30/2019
Rev 02
Page 6 of 11
Bottom of heater
guard location
Heater Screws
Location
13.
Determine power requirements and wire size needed based on the room model.
Room
Sauna Heater
kW
Phase VAC
Sauna
Amps
WIRE SIZE
Power Supply to CB Box
CB Box to Tradional Heater
HM
55C
Designer 4.5
4.5
1
240
18.8
2 #10AWG + GR
2 #10AWG + GR
HM
66C
Designer 6.0
6.0
1
240
25.0
2 #10AWG + GR
2 #10AWG + GR
NOTE: All installation and service to this equipment should be performed
by qualified licensed personnel in accordance with local and national
codes.
NOTE: A GFCI (Ground Fault Interrupt Circuit) device is not required
by NEC. A GFCI may be installed if required by local codes but will
nuisance trip during use of the product.
CAUTION: Loose wire connections can cause heat damage to wires,
terminal blocks and other components and may void the warranty.
14.
Connect wires from building electrical supply to the lower terminal
block labeled L1, L2, and Gnd. (Building wire is not supplied)
15.
Connect wires from the heater to upper terminal block labeled T1,
T2, and Gnd to the sauna heater.
16.
Mount the CB Box to the right wall with 4 screws provided by
locating the lower left corner of the box to wood corner trim on wall.
17.
Place cover on CB Box with the four screws provided.
18.
Hang heater on front wall. The wall is labeled and
predrilled for the top lag screws from the sauna heater
hardware.