Page
8
SmartFOAM
Foam calibration:
Enter the foam calibration screen
1. Press the MENU button to go to the system menu.
2. Press the Calibration/Configuration button on the
system menu screen.
3. Use the touch screen keypad to enter the password
1560
.
a. Press the “Enter” touch screen button to
submit the password.
b. Press the “Delete last digit” touch screen
button to erase the last digit entered.
c. Press the “Delete all digits” touch screen
button to erase all of the digits entered.
Calibrate the foam
1. Place a graduated measure container at the outlet of
the bypass hose capable of containing the expected
volume of foam concentrate.
2. Start the Hale SmartFOAM foam pump by pressing
the Start/Stop button.
3. Watch the level of foam in the graduated measure
container and stop the foam pump when at the
desired level by pressing the Start/Stop button again.
4. Adjust the reading in the foam total display to match
the actual volume by using the INCR and DECR
arrow buttons.
5. Press the SAVE button.
6. Repeat the procedure to verify that the setting is
correct.
7. Press the MENU button to exit the foam calibration
screen.
Summary of Contents for SmartFOAM 3.3
Page 3: ...Page 2 SmartFOAM NOTES...