A Series Card-type PLC - Digital Module User Manual

5 / 6

7. Digital Input/Output (DI/DO) Wiring Diagram

8. Terminal Wiring Diagram

9. Module Parameter Table

(CR code is corresponding to the Modbus register address)

Note: CR code is corresponding to the Modbus register address, the gray parts are read-only ,the white parts are readable
and writable.

CR

功能说明

A08DI

A08DOR

A08DOT

A08DOP

A08XDR

A08XDT

A08XDP

A16DI

A16DOR

A16DOT

A16DOP

A16XDR

A16XDT

A16XDP

00H

Low byte for module code, and high byte for module version number.

01H

Communication address

02H

Communication protocol: The low 4-bit of the low byte: 0 - N,8,2 For RTU

1 - E,8,1 For RTU

2 - O,8,1 For RTU

3 - N,7,2 For

ASCII

4 - E,7,1 For ASCII

5 - O,7,1 For ASCII

6 - N,8, 1 For RTU

The high 4-bit of the low byte: 0 – 2400

1 – 4800

2 – 9600

3 – 19200

4 – 38400

5 – 57600

6 - 115200

03H~06H

Module name

07H~08H

Default IP address: 192.168.1.111

09~0AH

Reserve

0BH

High byte subnet mask (b3~b0,1indicates 255, 0 indicates 0, for example, subnet mask255.255.255.0

b3~b0=1110), low byte

Reserved

0CH~0EH

Reserve

0FH

Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V

power supply

10H~4FH

DI channel 1~64 input value

50H~8FH

DO channel 1~64 output value

90H

DI filter time ms

0 - 0.8

1 - 1.6

2 - 3.2

3 - 6.4

4 - 12.8

5 - 25.6

6 - 51.2

91H~9FH

Reserve

Summary of Contents for A Series

Page 1: ...Xiamen Haiwell Technology Co Ltd www haiwell com A16DI 0 4 8 12 1 5 9 13 2 6 10 14 3 7 11 15 PWR LINK Digital Module User Manual Haiwell PLC User Manual A Series Card type PLC ...

Page 2: ...ion 3 2 Indicator Description 4 3 Power Supply Specification 4 4 Environmental Specifications for Product 4 5 Digital Input DI Specification 4 6 Digital Output DO Specification 4 7 Digital Input Output DI DO Wiring Diagram 5 8 Terminal Wiring Diagram 5 9 Module Parameter Table 5 10 Extend module Installation 6 ...

Page 3: ...DC24V 0 1A MAX A16DOR DC24V 0 35A MAX A16DOT DC24V 0 35A MAX A16DOP DC24V 0 35A MAX A16XDR DC24V 0 2A MAX A16XDT DC24V 0 2A MAX A16XDP DC24V 0 2A MAX A16DI 0 4 8 12 1 5 9 13 2 6 10 14 3 7 11 15 PWR RUN 1 3 S S X0 X1 X2 X3 X4 X5 X6 X7 X8 S S X9 X10 X11 X12 X13 X14 X15 4 5 2 6 7 8 9 95 0 25 0 65 0 14 0 1 Digital channel indicator 8 Module expansion port 2 PWR power indicator link running indicator 9...

Page 4: ...age for input and expansion None Isolation type No Electrical isolation Power protection DC input power polarity reverse over voltage protection 4 Environmental Specifications for Product Item Environment Specification Temperature Humidity Operating temperature 0 55 Storage temperature 25 70 Humidity 5 95 RH No condensation Vibration resistance 10 57 HZ amplitude 0 075mm 57HZ 150HZ acceleration 1G...

Page 5: ...munication protocol The low 4 bit of the low byte 0 N 8 2 For RTU 1 E 8 1 For RTU 2 O 8 1 For RTU 3 N 7 2 For ASCII 4 E 7 1 For ASCII 5 O 7 1 For ASCII 6 N 8 1 For RTU The high 4 bit of the low byte 0 2400 1 4800 2 9600 3 19200 4 38400 5 57600 6 115200 03H 06H Module name 07H 08H Default IP address 192 168 1 111 09 0AH Reserve 0BH High byte subnet mask b3 b0 1indicates 255 0 indicates 0 for exampl...

Page 6: ...parallel interface on the lower right side of the previous module host or expansion module is inserted into the parallel interface on the lower left side of the next module and hooked with small cards on both sides The parallel interface on the right side of this module is used as the next expansion module Connect all expansion modules in this way in sequence Thanks for choosing Haiwell Products I...

Reviews: