background image

HaiLin Controls

 

                      Page 1 of 2

NON-PROGRAMMABLE

 

DIGITAL THERMOSTAT 

HL-ESNC-025 (220V) / HL-ESND-026 (24V) 

-Large, Easy To Read Display 

-Blue Backlight 

-

Fahrenheit or Centigrade

 

-Cool

Heat and Automatic Heat/Cool Changeover 

-Keypad Lock 

-Auto Recovery 

Specification 

Set-Point Range: 5

℃~

35

 (41

℉~

95

 )

 

Operating difference: 

±

 1

Switch current rating: 

<

 2 A 

Sensing element : NTC 

Display: LCD 

Power supply:   

HL-ESNC-023/ HL-ESND-023: 220V AC

±

10%, 50Hz 

HL-ESNC-024/ HL-ESND-024: 24V AC, 50Hz 

Dimension: 86 × 86 × 35 mm ( W × H × D ) 

Housing: ABS Flame Retardant 

Basic Operation

 

Power ON/OFF 

"

 

To turn the thermostat on, press “

”. Mode symbol (

or 

), 

“RT”, and room temperature will be displayed

"

 To turn the thermostat off, press “

” again. There is no any display 

on LCD and no any output. 

Select Mode 

"

 

Cool Setting

Press “

”, the “SET” icon will flash, until the “

” is 

displayed, it will be confirmed automatically after 6 seconds; 

"

 

Heat Setting

Press “

”, the “SET” icon will flash, until the “

” is 

displayed, it will be confirmed automatically after 6 seconds; 

"

 Auto Setting

Press “

”, the “SET” icon will flash, until the “

” is 

displayed, it will be confirmed automatically after 6 seconds. 

NOTE: 

"

 Heating Mode: When the heating temperature is higher than the 

current room temperature, it will display 

” and the thermostat will turn 

on; otherwise, it will flash “

” and the thermostat will turn off; 

"

 Cooling Mode: When the cooling temperature is lower than the 

current room temperature, it will display 

” and the thermostat will turn 

on; otherwise, it will flash “

” and the thermostat will turn off; 

"

 Auto Mode

It will display 

 and the working mode active status 

refers to the cool and the heat working mode, when does not satisfy the 

above condition, the thermostat will have no output and will stop. 

Select Desired Temperature 

"

 

Press the UP or DOWN buttons until the desired heating or cooling 

temperature set point is displayed. 

"

 

Press the MODE button to select the second temperature setting 

(either HEAT or COOL)

   

Setting fan operation 

Press the Fan button to switch among 

Hi

)、 (

Med

、 (

Low

)、

 

and AUTO fan settings. When the Hi, Med or Low mode is selected, the 

fan runs continuously for improved air circulation. 

When the AUTO mode is selected, the fan runs only as needed to 

maintain the desired indoor temperature. 

Service filter feature 

"

 

The thermostat reminds you when it’s time to change or clean the 

filter by displaying the “

” indicator. 

"

 

Hold the Fan button down for approximately 5 seconds after you 

have changed or cleared your filter to reset the timer. Then the “

” will 

be turned off and filter timer cleared manually.   

Checking the outdoor temperature 

"

 

Hold the Mode button down for approximately 5 seconds. 

"

 

Outdoor temperature will be displayed for about 5 seconds. 

NOTE:

 If “E2” is displayed, the thermostat does not include the outdoor 

temperature function or the function is not properly check with your 

dealer if you are unsure. 

(Only used in 

HL-ESND-023 and HL-ESND-024 

model) 

OPERATIONAL INFORMATION

 

Compressor Timeguard 

"

 

This timer prevents the compressor from starting unless it has been 

off for at least 5 minutes. It can be defeated for 1 cycle by 

simultaneously 

pressing the FAN mode button and the UP button.(

 

Option 12 default 

setting is 3 ) 

Minimum On Time 

"

 

In normal operation, when a stage turns on, it will not turn off for a 

minimum of 3 minutes. (Option 13 default setting is 3) 

Auto Changeover 

"

 

When the auto changeover mode is selected, a change from heat to 

cool (or vice versa) will not occur until an opposite mode demand has 

existed for 20 minutes. If the set point is changed, the 20 minute 

requirement is deleted. Auto mode may be disabled. (Option 14 default 

setting is 20 ) 

Heat On and Cool On Icons 

"

 

When a heating or cooling demand exists, the HEAT ON or COOL 

ON icon will either remain on or flash. If flashing, the equipment is 

temporarily prevented from turning on by one of the timers. While the 

icon remains on without flashing, the equipment is on. 

Error Codes 

E1 — If the thermostat cannot properly read room temperature, and it 

needs to be adjusted, E1 will be displayed. 

E2 — If the thermostat cannot properly read outdoor temperature, and it 

needs to be adjusted, E2 will flash alternately with room temperature. 

F1— Keypad is locked.   

Set Thermostat Configuration 

"

 

Configuration options are intended to be selected at installation and 

normally should not be modified by the home owner. These options are 

not discussed in the Homeowner’s Guide and therefore must be made 

as part of the installation. A special procedure allows entry in to the 

configuration mode. The thermostat will automatically exit this if no 

button is pressed for 90 seconds.   

"

 

An explanation for each of these and how to enter the configuration 

mode follows. 

To enter the configuration mode 

"

 

Turn off the thermostat and hold the fan button down for 

approximately 15 seconds. After 15 seconds, Option “01” will appear in 

the display. 

OPTION 01 – OUTDOOR SENSOR SETTING 

"

 

This option is used to choose whether the outdoor sensor exists. If 

the thermostat connected the outdoor sensor, set this option ON, 

otherwise set OF. 

TO ADJUST: 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 01.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 01 setting.

4. Use Up and Down buttons to move between the available Option 01

choices of ON or OF. Factory default is OF.

5. Press Mode button again to return to Option 01. The SET icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode. 

OPTION 02 – CLEAN FILTER TIMER 

"

 

This option selects the number of hours of blower operation (Heating, 

cooling, or fan).Time selection can be from 400 to 3600 hours by 

selecting numbers from 1 to 9. (Time is 400 X number selected.) 

Factory default is 2 (800 hours).Recommended selection are : 

disposable filter 800 hours, media filter 1200 to 1600 hours, or 

electronic air cleaner 1600 to 2400 hours of blower operation. 

TO ADJUST: 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 02.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 02 setting.   

4. Use Up and Down buttons to move between the available Option 02

values 1 to 9. Factory default is 2.

5. Press Mode button again to return to Option 02. The “SET” icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode. 

OPTION 03 –FAHRENHEIT/ CELSIUS SELECTION 

"

 

This option selects Fahrenheit or Celsius operation. 

TO ADJUST:   

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 03.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 03 setting.

4. Use Up and Down buttons to move between the available Option 03

choices of F (Fahrenheit) or C (Celsius). Factory default is C.

5. Press Mode button again to return to Option 03. The SET icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode.

OPTION 04 –FAN (Hi. Med and Low) ON WITH W/W1 OUTPUT 

"

 

This selection determines whether the FAN output is to be ON or 

OFF when any W output is ON. Most furnaces and fan coils manage 

their own blowers and do not require a separate FAN signal. For these 

applications, select OFF. Some auxiliary heaters require a separate 

FAN signal to turn on the blower. In this case, select On. Factory default 

is OF (OFF).   

TO ADJUST

 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 04.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 04 setting.

4. Use Up and Down buttons to move between the available Option 04

choices of ON or OF. Factory default is OF. 

5. Press Mode button again to return to Option 04. The “SET” icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode.

OPTION 05 –INDOOR SENSOR SELECTING 

"

 

To use this function, option 01 must be set to be On and an outdoor 

sensor must be connected. Select ON, outdoor sensor will be replaced 

the building sensor and OPTION 08 will not work. Factory default is OF. 

TO ADJUST

 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 05.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 05 setting.

4. Use up and down buttons to move between the available Option 05

choices of ON or OF. Factory default is OF.

5. Press Mode button again to return to Option 05. The “SET” icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode.

OPTION 06

ROOM TEMPERATURE OFFSET 

"

 

This option allows calibration (or deliberate miscalibration) of room 

temperature sensor. There are various reasons why the home owners 

want to adjust the displayed temperature. The selected number is the 

number of degrees, plus or minus, which will be added to the actual 

temperature. The number can range between -5 and +5. Factory default 

is 0. This adjusted value will be used as actual temperature for both 

display and control action. For example, if 2 is selected, 72F actual will 

read 74F. If set point is 72, the room will control to an actual value of 70 

which will be displayed and acted upon as if it were 72. The effect is that 

a positive number selection will make the room temperature lower and 

vice versa. This thermostat is factory calibrated within an accuracy of 

plus or minus 1F, so this adjustment will provide the best accuracy when 

set to 0. 

TO ADJUST

 

1. Enter configuration mode (if not already there).

2. Use Up and Down buttons to display Option 06.The “SET” icon

should be off.

3. Press Mode button once. The “SET” icon will be come on. The

display now shows Option 06 setting.

4. Use Up and Down buttons to move between the available Option 06

choices of -5 t5 in 1 step. Factory default is 0.

5. Press Mode button again to return to Option 06. The “SET” icon will

now be off.

6. Use Up and Down buttons to select another Option, or press Power

button to exit configuration mode.

OPTION 07

AUTO MODE ON/OFF SELECTION 

"

 This option allows the installer to enable or disable AUTO mode 

Room temperature 

Set 

desired  

temperature 

Change mode 

Cool mode 

Heat mode 

Auto mode 

Service filter feature

 

Fan 

Power button 

Mode button 

Fan button

 

Up button

 

Down button

Shows room temperature,

desired 

temperature,

 and

other feature information

as required.

 

Reviews: