Haier Symptom Service Support Download Page 4

Service Support System 

 

 

CPN10XHJ

 

  Page 4 of 7 

 

The set 

temperature 

only shows on 

the display for 

a moment 

after 

adjustment 

(where 

applicable) 

This is normal operation, after 

adjusting the temperature the 

display reverts to the 

temperature value in the room. 

N/A 

N/A 

N/A 

N/A 

N/A 

No cooling, 

fans are 

running 

Verify the thermostat is set for 

a value ~ 10 degrees lower 

than the room temperature 

Verify the air filter is clear 

Verify there is nothing 

obstructing air flow through the 

exhaust kit 

Verify the water tank is empty , 

drain the tank if necessary 

1. Verify the thermostat 

is cycling the unit on and 

off properly. 

2. Inspect the wiring to 

the Control PCB. 

3. Verify the unit is 

properly charged with 

refrigerant 

P.C.B.-

CONTROL 

BOARD 

AC-

5210-

139  

N/A 

N/A 

No Cooling 

Fans are NOT 

running 

Verify the thermostat is set for 

a value ~ 10 degrees lower 

than the room temperature 

Verify the air filter is clear 

Verify there is nothing 

obstructing air flow through the 

exhaust kit 

Verify the water tank is empty , 

drain the tank if necessary 

1. Inspect the wiring 

from the Control PCB to 

the evaporator fan motor 

and condenser fan 

motor. 

2. Verify the continuity of 

the Overload protector. 

3. Verify the continuity of 

the compressor 

windings. 

P.C.B.-

CONTROL 

BOARD 

AC-

5210-

139  

Fan Motor 

AC-

4550-

309  

Summary of Contents for Symptom

Page 1: ...s to provide the technicians with repair advice that can be used to improve the first time fix ratio as well as reduce shotgun troubleshooting Model CPN10XHJ Modified Date 8 8 2012 Symptom Customer advice Repair Guidance Primary Part Description Primary Part Secondary Part Description Secon dary Part Musty Smell Verify the Exhaust kit is not obstructed Verify the water tank is not full If mold or ...

Page 2: ...Verify the thermostat is cycling the unit on and off properly 5 Verify the unit is properly charged with refrigerant WHEEL BLOWER CONDENS ER AC 8000 30 N A N A STOP is shown on the LCD display This indicates the internal water tank has filled with water and needs to be drained Open the drain plug on the back of the unit and allow the unit to drain into a shallow bowl 1 Inspect the drain tube and p...

Page 3: ...t is cycling the unit on and off properly 3 Inspect the wiring to the Control PCB 4 Verify the unit is properly charged with refrigerant WHEEL BLOWER CONDENS ER AC 8000 30 N A N A Cannot adjust the Temperature Temperature buttons do not work When using Dehumidify or Fan Mode the temperature adjustment button is disabled Inspect the wiring from the Display PCB to the Control PCB P C B CONTROL BOARD...

Page 4: ... necessary 1 Verify the thermostat is cycling the unit on and off properly 2 Inspect the wiring to the Control PCB 3 Verify the unit is properly charged with refrigerant P C B CONTROL BOARD AC 5210 139 N A N A No Cooling Fans are NOT running Verify the thermostat is set for a value 10 degrees lower than the room temperature Verify the air filter is clear Verify there is nothing obstructing air flo...

Page 5: ...000 30 Fan Motor AC 4550 309 A Household fuse has blown or a circuit Breaker has been tripped It is recommended that an AC unit have its own circuit Be sure the time delay fuse or circuit breaker of the correct capacity Do not use an extension cord with this or any other appliance You are trying to restart the air conditioner too soon after turning off the air conditioner Wait at least 3 minutes a...

Page 6: ...cy A higher capacity air conditioner may be required depending on the size of the room being cooled 1 Verify the thermostat is cycling the unit on and off properly 2 Inspect the wiring to the Control PCB 3 Verify the unit is properly charged with refrigerant P C B CONTROL BOARD AC 5210 139 N A N A Remote not working Verify the batteries are good Verify nothing is blocking the receiver Verify there...

Page 7: ...tability for their purposes prior to use In no event will Haier America Trading LLC be responsible for damages of any nature whatsoever resulting from the use of or reliance upon Information or the product to which Information refers Disclaimer 2 This material is published for informational purposes only and intended for use only by persons qualified for the specific tasks shown Qualified personne...

Reviews: