Installations
Domestic air conditioner
30
10.3.3 Indoor fan motor malfunction
Indoor Display
E14
Method of
The rotation speed detected by the Hall IC during fan motor operation is used to determine
Malfunction
abnormal fan motor operation
Detection
Malfunction
when the detected rotation feedback signal don’t received in 2 minutes
Decision
Conditions
Supposed Causes
Operation halt due to breaking of wire inside the fan motor.
Operation halt due to breaking of the fan motor lead wires.
Detection error due to faulty indoor unit PCB.
How to check Fan Motor (DC)
1. Check connector connection.
2. Check motor power supply voltage output (pins 1-4).
3. Check motor control voltage (pins 4-5).
4. Check rotation command voltage output (pins 4-6).
5. Check rotation pulse input (pins 4-7).
Notes: the a/c is electrifying, don’t pull out or insert the terminals of the
motor, else the motor would be damaged.
Troubleshooting * Caution
Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
10.3.4 Outdoor DC fan motor fault
Outdoor display LED1 flash 9 times
Method of DC fan motor is detected by checking the fan running condition and so on
Malfunction
Detection
Malfunction when the data of EEPROM is error or the EEPROM is damaged
Decision
Conditions
Supposed
■
DC fan motor protection dues to the DC fan motor faulty
Causes
■
DC fan motor protection dues to faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage
may be occurred.
Summary of Contents for SUPER MATCH AS35S2SF1FA-BC
Page 12: ...Piping diagrams Domestic air conditioner 5 Piping diagrams 10 Expansion valve Expansion valve ...
Page 43: ...Table of Contents Domestic air conditioner 40 11 Wiring diagrams 11 1 INDOOR UNIT ...
Page 44: ...Circuit diagrams Domestic air conditioner 41 11 2 Circuit Diagrams ...
Page 49: ...four 5 Removal Procedure 4 Domestic Air Conditioner 1 2 3 four Remove the casing ...
Page 53: ...Removal Procedure 8 Domestic Air Conditioner motor cover ...
Page 54: ...Removal Procedure 9 Domestic Air Conditioner ...