Remedy
Dismantle the system. Remove the dry filter and purge the tubing with
nitrogen. Next, install a new filter. Then evacuate it and fill with refrigerant.
4)
Clogged Filter
Analysis of Problem
The complete clogging of the filter rarely occurs. Oftentimes, there is an
accumulation of paste-like matter formed from dust on the filter. Tapping the
filter may remove part of the paste-like matter. When the filter is clogged, it will
be cooler than normal.
Remedy
The same as described for the capillary clogged with dirt.
Compressor Problems
1) Broken Gas Suction And Discharge Valve Blocks
Analysis of Problem
The compressor works by opening and closing the gas suction valve and
discharge valve to suck and discharge the refrigerant. If the valve block is
broken, the refrigerant cannot be discharged. This prevents refrigeration.
Remedy
It is quite difficult to differentiate this trouble from others because they have
similar symptoms. When repairing, listen attentively for abnormal sounds coming
from the compressor. Oftentimes, broken pieces of valve block strike against the
cylinder. Check to see if the compressor casing is too hot. Secondly, measure the
pressures at the high and low-pressure ports of the compressor with pressure
gauges. If the gas suction valve block is broken, the suction pressure gauge
pointer will swing violently and the suction pressure will be very high. Whereas
when the gas discharge valve block is broken, the discharge pressure gauge
pointer will swing drastically and the discharge pressure will be very high. In both
cases, stop the compressor at once. If possible, open the cylinder cover, check
the valve block, and repair it.
Compressor suddenly stops
Very often, when the compressor suddenly stops, the gas suction pressure and/or
discharge pressure have exceeded their respective prescribed ranges. When this
happens, the pressure-operated protective relay automatically shuts off the power
to the compressor. Below we discuss the reasons for high gas discharge pressure
and low suction pressure.
Stoppage due to excessively high gas discharge pressure
1) High gas discharge pressure due to excess refrigerant