8
Refrigerant Line Sizing
Check the following table (
Table 3
) for correct suction and liquid line sizes for any combination of
the unit size and the maximum refrigerant line length.
Table 3:Refrigerant Line Sizing
The factory charge is sufficient for 15 feet of standard liquid line. For longer or shorter liquid line
lengths, adjust the charge as follows:
1/4" Line +/- 0.3 oz. Per foot
5/16" Line
+/- 0.4 oz. Per foot
3/8" Line
+/- 0.6 oz. Per foot
1/2" Line
+/- 1.2 oz. Per foot.
Vertical Separation between Indoor and Outdoor Units
Maximum allowable vertical separations between indoor and outdoor units are illustrated in
Figure
4-B-1 and Figure 4-B-2
. It's 70' when the indoor unit is below the outdoor unit (Figure 4-B-1), and 50'
when the indoor unit is above the outdoor unit (Figure 4-B-2).
To ensure good oil return to the compressor when the indoor unit is below the outdoor unit, suction
line oil trap should be used as illustrated in Figure 4-B-1.
Tubing Connections
! CAUTION
- Use extreme caution in removing the caps from the suction and liquid line fittings, as
there is pressure present. A fitting is on the liquid line to remove pressure.
! CAUTION
- Heat Pumps are charged with refrigerant. Heat Pump liquid and suction valves are
closed to contain the charge within the unit. Do not force the valve stem against the retaining ring. If
the valve stem is backed out past the retaining ring, system pressure could force the valve stem out
of the valve body and possibly cause personal injury.
! CAUTION
- The piston is in the accessory bag. Don't forget to take it out and put into the indoor
liquid pipe orifice.
Instructions on the field tubing connections and valve opening procedure are as follow:
Suction
Liquid
Suction
Liquid
Suction
Liquid
1.5
3/4
3/8
3/4
3/8
3/4
3/8
13
2.0
3/4
3/8
3/4
3/8
3/4
3/8
13
2.5
7/8
3/8
7/8
3/8
7/8
3/8
13
3.0
7/8
3/8
7/8
3/8
7/8
3/8
13
3.5
7/8
3/8
7/8
3/8
1 1/8
3/8
13
4.0
7/8
3/8
1 1/8
3/8
1 1/8
1/2
13
5.0
7/8
3/8
1 1/8
1/2
1 1/8
1/2
13
Unit Size
(Ton)
Refrigerant Line Length (Ft)
Up to 25
26-50
51-75
Seer
Summary of Contents for HR18D2VAE
Page 13: ...5 11 ...