507789-02G / 31-5000673-1
Issue 2336
Page 21 of 24
Heat Jumper
The HEAT jumper is used to determine CFM during electric
heat operation only. These jumper selections are activated
RQO\ZKHQ:LVHQHUJL]HG
Delay Jumper
7KH '(/$< MXPSHU LV XVHG WR VHW WKH VSHFL¿F PRWRU
fan operation during cooling mode. Depending on the
application, one of four options may be chosen by moving
the jumper to the appropriate set of pins.
#1 Pins Jumpered
a.
0RWRUUXQVDWXQWLOGHPDQGLVVDWLV¿HG
b.
2QFHGHPDQGLVPHWPRWRUUDPSVGRZQWRVWRS
OFF
OFF
A
B
100% CFM
COOLING
DEMAND
#2 Pins Jumpered
a.
0RWRUUXQVDWXQWLOGHPDQGLVVDWLV¿HG
b.
2QFHGHPDQGLVPHWPRWRUUXQVDWIRU
seconds.
c.
0RWRUUDPSVGRZQWRVWRS
OFF
OFF
A
B
C
100% CFM
100% CFM
(60 seconds)
COOLING DEMAND
#3 Pins Jumpered
a.
0RWRU UXQV DW IRU DSSUR[LPDWHO\
PLQXWHV ,I GHPDQG KDV QRW EHHQ VDWLV¿HG DIWHU
PLQXWHV
b.
0RWRUUXQVDWXQWLOGHPDQGLVVDWLV¿HG
c.
2QFHGHPDQGLVPHWPRWRUUDPSVGRZQWRVWRS
OFF
OFF
A
B
C
82%CFM
100% CFM
COOLING DEMAND
7 1/2 MIN
#4 Pins Jumpered
a.
0RWRUUDPSVXSWR
b.
0RWRU WKHQ UXQV DW IRU DSSUR[LPDWHO\
PLQXWHV ,I GHPDQG KDV QRW EHHQ VDWLV¿HG DIWHU
PLQXWHV
c.
0RWRUUXQVDWXQWLOGHPDQGLVVDWLV¿HG
d.
2QFHGHPDQGLVPHWPRWRUUDPSVGRZQWRVWRS
A
B
OFF
OFF
C
D
E
COOLING DEMAND
7 1/2 MIN
82% CFM
100%
CFM
Checkout Procedures
NOTE:
5HIHU WR RXWGRRU XQLW LQVWDOODWLRQ LQVWUXFWLRQV IRU
V\VWHP VWDUWXS LQVWUXFWLRQV DQG UHIULJHUDQW FKDUJLQJ
LQVWUXFWLRQV
Pre-Start-Up Checks
•
Is the air handler properly and securely installed?
•
,IKRUL]RQWDOO\FRQ¿JXUHGLVWKHXQLWVORSHGXSWR
LQFKWRZDUGGUDLQOLQHV"
•
Will the unit be accessible for servicing?
•
Has an auxiliary pan been provided under the unit
ZLWKVHSDUDWHGUDLQIRUXQLWVLQVWDOOHGDERYHD¿QLVKHG
FHLOLQJRULQDQ\LQVWDOODWLRQZKHUHFRQGHQVDWHRYHUÀRZ
could cause damage?
•
Have ALL unused drain pan ports been properly
plugged?
•
Has the condensate line been properly sized, run,
trapped, pitched, and tested?
•
Is the duct system correctly sized, run, sealed, and
insulated?
•
+DYHDOOFDELQHWRSHQLQJVDQGZLULQJEHHQVHDOHG"
•
Is the indoor coil factory-installed TXV properly sized
for the outdoor unit being used?
•
Have all unused parts and packaging been disposed
of?
•
,VWKH¿OWHUFOHDQLQSODFHDQGRIDGHTXDWHVL]H"
•
,VWKHZLULQJQHDWFRUUHFWDQGLQDFFRUGDQFHZLWKWKH
ZLULQJGLDJUDP"
•
Is the unit properly grounded and protected (fused)?
•
,V WKH WKHUPRVWDW FRUUHFWO\ ZLUHG DQG LQ D JRRG
location?
•
Are all access panels in place and secure?
Check Blower Operation
1.
6HWWKHUPRVWDWWR)$1217KHLQGRRUEORZHUVKRXOG
come on.
Check Cooling Operation
1.
Set thermostat to force a call for cooling (approximately
)ORZHUWKDQWKHLQGRRUDPELHQWWHPSHUDWXUH
2.
The outdoor unit should come on immediately and the
LQGRRU EORZHU VKRXOG VWDUW EHWZHHQ VHFRQGV
later.