5
Model
AU48NFIERA (G)
AU60NFIERA (G)
Outdoor coil
Number of rows
2
2
Tube pitch (a)
×
row pitch (b)
mm
19.05×22
19.05×22
Fin spacing
mm
1.5
1.5
Fin type (code)
HYDROPHILIC
ALUMINIUM
HYDROPHILIC
ALUMINIUM
Fin coating type
Optional
Clear lacquer
Clear lacquer
Salt spray test duration
Hour
168
168
Tube outside dia. and type
INNERGROOVE TUBE
INNERGROOVE TUBE
mm
Ф8
Ф8
Coil length
×
height
mm
970×1200
970×1200
Number of circuits
6
6
Cabinet coating
Coating type
Powder coating
Powder coating
Salt spray test duration
Hour
72
72
Sheet metal material
Hot zinc plate
Hot zinc plate
Sheet metal thickness
mm
0.8
0.8
Control panel enclosure IP class
Standard
IP24
IP24
Outdoor air flow
m
3
/h
6500
6500
Outdoor sound level (sound pressure level )
dB (A)
59
60
Outdoor sound level (sound power level )
dB (A)
70
71
Outdoor unit
Dimension (W*H*D)
mm
960×380×1250
960×380×1250
Packing (W*H*D)
mm
1095×410×1400
1095×410×1400
Net weight
kg
105
105
Gross weight
kg
113
113
Refrigerant
Type
R410A
R410A
Charged volume
kg
4
4
Throttle type
EXV
EXV
Design pressure
MPa
4.15
4.15
Refrigerant piping
Liquid pipe
mm
9.52
9.52
Gas pipe
mm
19.05
19.05
Total pipe length
m
100
100
Max. pipe length
(Equivalent/ Actual)
m
70
70
Max. Diff. indoor/outdoor unit
m
30 (Outdoor higher than indoor)
20 (Indoor higher than outdoor)
Max. Diff. indoor/indoor unit
m
10
10
Connectable indoor unit ratio
%
50%~130%
50%~130%
Maximum indoor units
Piece
8
9
Connection wiring
Power wiring
mm
2
4
4
Signal wiring
mm
2
Shield wire: (0.75-2)*2
Shield wire: (0.75-2)*2
Operation range
°C
Cooling: -15~43
Heating: -15~21
Cooling: -15~43
Heating: -15~21
Nominal condition:
Indoor temperature (cooling): 27 DB(°C)/19 WB(°C), indoor temperature (heating): 20 DB(°C)/14.5 WB(°C).
Outdoor temperature (cooling): 35 DB(°C)/24 WB(°C), outdoor temperature (heating): 7 DB(°C)/6 WB(°C).
The data is measured with 7.5m equivalent pipe and 0m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a
real time analyser calibrated sound intensity meter. It is a sound pressure noise level.