Trouble shooting
24
FAILURE
CODE
STATE OF
LED 5-4-3-2-1
TROUBLE
SHOOTING
POSSIBLE REASONS
DC fan motor fault
Fan is blocked, or the terminal is disconnected from
the PCB
Faulty 4-way valve
switching on
Coil of 4-way valve is disconnected, or faulty outdoor
PCB
Abnormal communication
between main PCB and
SPDU(or ISPM)
Communication cables broken, or not be well
connected, or faulty main PCB, or faulty SPDU(or
ISPM)
Compressor be locked
Faulty compressor or SPDU(or ISPM)
Compressor vibration too big
Faulty compressor
Compressor lose position
Faulty SPDU(or ISPM)
Faulty compressor start
Faulty compressor or SPDU(or ISPM)
Faulty position checking
circuit
Faulty SPDU(or ISPM)
Compressor broken
Faulty compressor or SPDU(or ISPM)
15
16
25
26
27
28
29
30
31
1
Faulty defrost sensor Te
Sensor disconnected, or broken, or short circuit
Faulty sensor Tao
Sensor disconnected, or broken, or short circuit
2
Faulty sensor Ts
Sensor disconnected, or broken, or short circuit
3
Faulty sensor Td
Sensor disconnected, or broken, or short circuit
4
Input overcurrent
Over current of the system, or broken of the current
sensor,or malfunction with indoor or outdoor fan
motors, or faulty PCB.
5
Abnormal communication
between indoor and outdoor
units
Wrong connection, or the wires be disconnected, or
wrong address setting of indoor units, or faulty PCB,
or faulty power supply
6
System high pressure
protection
High pressure switch is disconnected, or high pressure
switch worked, or Tc too high and faulty outdoor fan
motor when cooling, or faulty indoor fan motors when
heating, or refrigerant overabundance
9
System low pressure
protection
Low pressure switch is disconnected, or low pressure
switch worked, or Te too low and faulty outdoor fan
motors when heating, or faulty indoor fan motor when
cooling, or refrigerant shortage
10
IPM protection
IPM over current, or short circuit, or IPM temperature
too high, or IPM input voltage too low,or faulty SPDU
(or ISPM).
11
EEPROM fault
Faulty outdoor unit PCB
12
Over hot protection of
compressor
Serious lack of refrigerant of the system, or the
ambient temperature too high, or PMVs be blocked
13
Over hot protection of SPDU
(or ISPM)
Ambient tempreatrue too high, or outdoor fan be
blocked, or bad air circulation of outdoor unit
14
Faulty sensor Tc
Sensor disconnected, or broken, or short circuit
17
Faulty sensor Toci
Sensor disconnected, or broken, or short circuit
21
Low voltage protection
VDC<194V, too low voltage from power source
23
24
High voltage protection
VDC>400V, too high voltage from power source
Take off the plastic cover on the right side of the unit, you can find the LEDs near the communication
terminal. Symbol means the LED is ON, and symbol means the LED is OFF.