1. Applicable ambient temperature range:
The machine is adaptive in following situation
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on the indoor PC board is broken please change it with the type of T 3.15A /250V(For ADH105,
ADH125,ADH140M1ERG);or the type T5A /250V(For ADH071M1ERG,ADH071M3ERG,ADH090M1ERG).T8A/250V(For
ADH105/125/140/160H1ERG)
4. The wiring method should be in line with the local wiring standard.
5. The power cable should be:
H05RN-F 3G 4.0mm
2
(outdoor unit 1UH071/090/105N1ERG),
or H05RN-F 3G 6.0mm
2
(outdoor unit 1UH125/140/160P1ERG),
or H05RN-F 5G 4.0mm
2
(outdoor unit 1UH125/140P1EK);
The connecting cable should be:
H05RN-F4G 2.5mm
2
;
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grounding wire is the last one to be broken off.
6. The power cable and connect cable should be self-provided.
7. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm.
8. The indoor unit installation height is at least 2.5m.
9. A leakage breaker must be installed.
10.
10.1 FOR ADH071M1ERG, ADH090M1ERG, we can get the 4 different ESP through adjust the indoor unit PCB SW1-4
and SW1-5, please refer below:
Attention:
Cut off the power supply to adjust the SW1-4, and SW1-5, or else the operation is invalid.
10.2 For ADH071M3ERG, ADH105M1ERG, ADH125M1ERG, ADH140M1ERG, ADH105H1ERG, ADH125H1ERG,
ADH140H1ERG,ADH160H1ERG,static pressure selection need achieved by wired controller, refer wired controller's manual
to get details
SW1
(1)
(2) (3) (4) (5) (6) (7) (8) Static pressure
10 Pa
30 Pa
50 Pa
70 Pa
OFF OFF
OFF ON
ON OFF
ON ON
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7
Safety Precautions
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
43/26 C
10/6 C
27 C
15 C
24/18 C
-15 C
For AD105/125/140M1ERG,
ADH071M3ERG,
ADH105/125/140/160H1ERG,static pressure level selection can also
be achieved by Infrared remote controller,method is:
Step a: set the Infrared remote controller at condition:FAN mode,fan speed high.
Step b:then aim the remote controller at the infrared remote receiver RE-02,press HEALTH button 4+N times(1 N
10,integer) within 12 seconds,then the receiver will beep N+1 times,the static pressure level N is been set successfully.
Note:For Infrared remote controller YR-HBS01, need press ON/OFF button make the controller's at OFF status
first,then open the button cover press FRESH button will enter FAN mode interface.
ADH105M1ERG
ADH125M1ERG
ADH140M1ERG
ADH105H1ERG
ADH125H1ERG
ADH140H1ERG
ADH160H1ERG
40
50
60
80
100
120
150
180
200
250
Static pressure level ( N)
External static pressure
1
2
3
4
5
6
30
40
50
60
70
80
7
8
9
10
90
100
110
120
(pa)
ADH071M3ERG
25
37
50
70
90
100
110
120
130
150