8.11 Refrigerant
MRV central air conditioner uses refrigerant “R22”. This refrigerant itself is innocuous, non-combustible
safety refrigerant. But then, when arranging the air conditioner equipment, it is necessary to
take some steps to take precautions against in case of the indoors refrigerant leakage. Such as,
the room size shall be taken into account to avoid making the concentration of the refrigerant
not exceed the concentration limit and other relevant steps. The concentration limit is the
concentration that is not harmful to human body and can take emergency steps to treat the
concentration of Freon.
Concentration limit of R22: 0.3kg/m3
1.
Sequence of refrigerant concentration affirmance
Calculate the refrigerant concentration according to the following sequence.
(1)
Calculate the total refrigerant-charging amount of each of the refrigerating system (kg).
l
Refrigerant charging amount of outdoor Additional refrigerant charging amount
= Total refrigerant charging amount of the refrigerating equipment (kg).
l
Refrigerant charging amount of outdoor system: Refrigerant charging amount when air
conditioner leaves factory.
l
Additional refrigerant charging amount: Additional refrigerant charging amount
according to the site pipe length and pipe diameter.
(2)
Calculate the minimum size of the room suitable for the indoor unit assembly (m3).
(3)
Calculate the concentration of refrigerant:
Total refrigerant charging amount of refrigerating equipment/the minimum room size suitable
for indoor unit assembly (m3)
≤
Refrigerant concentration limit: 0.3kg/ m3
2.
Countermeasure when exceeding the concentration limit
(1)
Set an effective opening for ventilation and fresh air.
l
Cut an intake respectively on the upper and lower part of the door which areas are
equivalent to 0.15% grounding area, or cut an intake in other part of the room.
(2)
Reduce the total refrigerant charging amount of the refrigerating equipment
l
Shorten the refrigerant pipe length. Reduce the installation place distance between the
outdoor unit and the indoor unit to shorten the refrigerant pipe length, so that reduce the
total refrigerant charging amount of the refrigerating equipment.
(3)
Establish ventilation and fresh air system
l
Establish a mechanical equipment for fresh air to keep the refrigerant concentration
below the concentration limit (normal ventilation)\
l
When can not ventilate the normally, please set an alarm apparatus linked with the
mechanical ventilation equipment.
Summary of Contents for AB092FCAHA
Page 1: ...Home MRV Service Manual 2003 08 SYJS 0308 ...
Page 32: ......
Page 36: ...2 Model AU422FIAIA AU422FIBIA ...
Page 37: ...3 model AU242FHAHA AU242FHBHA ...
Page 44: ...0010570373 9 Model AD142FCBHA AD182FCBHA 8 Model AF092FCBHA AF122FCBHA ...
Page 47: ...4 2 Circuit Diagram 4 2 1 Indoor unit Model AS092FMAHA AS092FMBHA ...
Page 48: ...Model expansion valve MRV circuit diagram of control board for electrical expansion valve ...
Page 49: ...Model AS182FTAHA AS182FTBHA ...
Page 50: ...Model AB182FCAHA AB182FCBHA AB092FCBHA AB142FCBHA ...
Page 51: ...Model AC182FCAHA AC182FCBHA AC142FCBHA ...
Page 52: ...Model AD142FCBHIA AD182FCBHIA ...
Page 53: ...Model AE092FCAHA AE092FCBHA AE182FCAHA AE182FCBHA ...
Page 54: ...MP3 circuit diagram ...
Page 55: ...Model AP182FAAHA ...
Page 56: ...Model AE112FCBIA AE182FCBIA TES ...
Page 57: ...Model AF092FCBHA AF122FCBHA ...
Page 58: ...Model AP182FAAHA AP182FABHA ...
Page 59: ...4 2 2 Outdoor unit Model AU422FIAHA AU422FIAIA AU422FIBIA Control PCB schematic ...
Page 60: ...Power PCB schematic ...
Page 61: ...AU24FAAHA AU242FHBHA Control PCB schematic Power PCB schematic ...
Page 94: ...5 Model AP182FAAHA 500 1746 250 ...
Page 113: ...Number of articles NO Accessory Parts 3 by 1 4 by 1 13 3 4 14 1 1 15 12 16 16 1 1 ...
Page 125: ...5 5 Installation of cassette type AB092 AB142 ...
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 135: ...9 1 Model AU422FIAHA AU422FIAIA AU422FIBIA 9 EXPLODED VIEWS PART LISTS ...
Page 138: ...Model AU482FIAIA AU48NFIAIA ...
Page 141: ...AU422FIAHA AU422FIAIA AU422FIBIA Electrical system ...
Page 144: ...Model AU242FHAHA AU242FHBHA ...
Page 147: ...MODEL AB092FCBHA AB142FCBHA AB182FCBHA ...
Page 150: ...MODEL AB092FCAHA AB142FCAHA ...
Page 153: ......
Page 155: ...Model AC142FCBHA AC182FCBHA AC182FCAHA ...
Page 158: ...Model AD142FCBHA AD182FCBHA ...
Page 160: ...Model AE092FCAHA AE092FCBHA AE182FCAHA AE182FCBHA ...
Page 163: ...Model AE092FCAKA AE182FCAKA ...
Page 165: ...MODEL AF092FCBHA AF122FCBHA ...
Page 167: ...MODEL AP182FAAHA AP182FABHA ...
Page 174: ...Sincere Forever ...