background image

Outdoor unit

1.Installation of Outdoor Unit

2.Connection of pipes

Install according to

To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius

should be 30 to 40 mm or longer.

Connecting the pipe of gas side first makes working easier.

The connection pipe is specialized for R410A.

Drawing for the installation of indoor and outdoor units

Half union

Flare nut

Forced fastening without careful

centering may damage the

threads and cause a leakage of

 gas.

Pipe Diameter

Fastening torque

Spanner

Torque wrench

Liquid side 6.35mm(1/4")

18N.m

Gas side 9.52mm(3/8")

Gas side 12.7mm(1/2")

42N.m

55N.m

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

The standard pipe length is 5m. If it is over 5m, the function of the unit will be affected. If the pipe has

to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant

must be conducted by professional air conditioner engineer. Before adding additional refrigerant,

perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge

additional refrigerant.

CAUTION

In case more than 5m

Oil trap shoud be installed every 5~7m

Max. Length:A=20m

Max.Elevation:10m

no more gas if the length of connecting pipe is less than35m

A

Outdoor unit

Indoor unit

Outdoor unit

Indoor unit

Oil trap

3.Connection

Use the same method on indoor unit. Loosen

the screws on terminal block and insert the

plugs fully into terminal block, then tighten the

screws.

Insert the cable according to terminal number

in the same manner as the indoor unit.

If wiring is not correct, proper operation can

not be carried out and controller may be

damaged.

Fix the cable with a clamp.

4.Attaching Drain-Elbow

 If the drain-elbow is used, please attach it as

 figure.

 Note: Only for heat pump unit.

Drain hose

Drain elbow

6

Summary of Contents for 1051

Page 1: ...parts for piping Mark Parts name Non adhesive tape Adhesive tape Saddle L S with screws Connecting electric cable for indoor and outdoor Drain hose Heating insulating material Piping hole cover No Accessory parts Remote controller R 03 dry battery Mounting plate Drain elbow 1 1 2 3 4 5 6 2 1 4 1 1 Number of articles Accessory parts Pipe supporting plate Arrangement of piping directions Rear left R...

Page 2: ...g the remote controller on a wall place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened Place which is less affected by rain or direct sunlight and is sufficiently ventilated Place possible to bear the unit where vibration and noise are not increased Place where discharged wind and noise do not cause a nuisance to the neighbors Place where a distance ...

Page 3: ...fter installation Section of wall hole Piping hole pipe Outdoor side Thickness of wall Indoor side Wall hole 60mm Indoor unit 1 Fitting of the Mounting Plate and Positioning of the wall Hole When the mounting plate is first fixed 1 Carry out based on the neighboring pillars or lintels a proper leveling for the plate to be fixed against the wall then temporarily fasten the plate with one steel nail...

Page 4: ...rain hose must be bound with refrigerant piping by protecting tape Cut away with a nipper the lid for piping according to the piping direction and then bend the pipe according to the position of wall hole When bending be careful not to crash pipes Connect beforehand the indoor outdoor electric cable and then pull out the connected to the heat insulation of connecting part specially Lid for right p...

Page 5: ...ted cable with the wiring cover Note When connecting the cable confirm the terminal number of indoor and outdoor units carefully If wiring is not correct proper operation can not be carried out and will cause defect 1 If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similar qualified person The type of connecting wire is H05RN F or H07RN F 2 If the fu...

Page 6: ...thened the refrigerant should be charged according to 20 g m But the charge of refrigerant must be conducted by professional air conditioner engineer Before adding additional refrigerant perform air purging from the refrigerant pipes and indoor unit using a vacuum pump then charge additional refrigerant CAUTION In case more than 5m Oil trap shoud be installed every 5 7m Max Length A 20m Max Elevat...

Page 7: ...ervice port open 2 way valve and 3 way Turn the valve rod anticlockwise until hitting lightly To prevent the gas leakage turn the service port s cap the valve rod s cap for 2 way valve and 3 way s a little more than the point where the torque increases suddenly After attaching the each caps check the gas leakage around the caps CAUTION 1 If the refrigerant of the air conditioner leaks it is necess...

Page 8: ...arried out Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below Please pour water in the drain pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly explain to our customers how to operate through th...

Page 9: ...duct is marked with this sym bol This means that electrical and electronic products shall not be mixed with unsorted household waste Do not try to dismantle the system yourself the dis mantling of the air conditioning system treatment of the refrigerant of oil and of other part must be done by a qualified installer in accordance with relevant local and national legislation Air conditioners must be...

Page 10: ...e los productos eléctricos y electrónicos no deben mezclarse con el resto de resi duos domésticos no clasificados No intente desmontar el sistema usted mismo El des mantelamiento del acondicionador de aire así como el tratamiento del refrigerante aceite y otros compo nentes debe ser efectuado por un instalador compe tente de acuerdo con las normas locales y nacionales aplicables Los acon dicionado...

Page 11: ... the additional refrigerant amount charged in the field and 1 2 the total refrigerant charge on the refrigerant charge label supplied with the product The filled out label must be adhered in the proximity of the product charging port e g onto the inside of the stop valve cover A contains fluorinated greenhouse gases covered by the Kyoto Protocol B factory refrigerant charge of the product see unit...

Page 12: ... refrigerante cargado en campo y 1 2 la carga total de refrigerante En la etiqueta de carga de refrigerante suministrada con el producto La etiqueta rellenada debe pegarse cerca de la conexión de carga del pro ducto p ej en el interior de la cubierta de la válvula de tope A Contiene los gases fluorados de efecto invernadora regulados por el Protocolo de Kioto B Carga de refrigerante de fábrica del...

Reviews: