Indoor unit

4.Connecting the indoor/outdoor Electric Cable

Fixing the indoor unit body

Removing the wiring cover

[Other direction piping]

Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.

Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according

to the position of wall hole. When bending, be careful not to crash pipes.

Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation

of connecting part specially.

Hang surely the unit body onto the upper notches of the

mounting plate. Move the body from side to side to verify

its secure fixing.

In order to fix the body onto the mounting plate,hold up

the body aslant from the underside and then put it down

perpendicularly.

Remove terminal cover at right bottom corner of indoor unit, then

take off wiring cover by removing its screws.

Heat insulation
material

Drain hose

Piping

Indoor/outdoor
electric cable

When connecting the cable after installing the indoor unit

1. Insert from outside the room cable into left side of the wall hole, in which
    the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable making a loop.

signal wire

 Change-for-fresh-air tube

1. Insert the drain hose into the dent of heat insulation materials of indoor unit.

2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then

    connect them.

3. Coat the flaring seal face with refrigerant oil and connect pipes.

    Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape

When connecting the cable before installing the indoor unit

Insert the cable from the back side of the unit, then pull it out on the front side.

Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.

Pull the cable slightly to make sure the cables have been properly inserted and tightened.

After the cable connection, never fail to fasten the connected cable with the wiring cover.

Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring

       is not correct, proper operation can not be carried out and will cause defect.

4

Lid for right piping

Lid for under piping

Lid for left piping

Fix with adhesive tape

Summary of Contents for 0010554405B

Page 1: ... of piping directions Rear left Rear right Left Below Right Connecting electric cable for indoor and outdoor Drain hose Heating insulating material 4X50 4X25 Piping hole cover Read this manual before installation 1 Driver 2 Hacksaw 3 Hole core drill 4 Spanner 17 19 and 26mm 5 Torque wrench 17mm 22mm 26mm 6 Pipe cutter 7 Flaring tool 8 Knife 9 Nipper 12 Reamer 10 Gas leakage detector or soap and wa...

Page 2: ... is sufficiently ventilated Place possible to bear the unit where vibration and noise are not increased Place where discharged wind and noise do not cause a nuisance to the neighbors Place where a distance marked is available as illustrated in the above figure Before inserting power plug into receptacle check the voltage without fail The power source is the same as the corresponding name plate Ins...

Page 3: ...Refer to the previous article When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a hole of 70 mm in diameter slightly descending to outside the wall Install piping hole cover and seal it off with putty after installation Section of wall hole Piping hole pipe...

Page 4: ... outside the room cable into left side of the wall hole in which the pipe has already existed 2 Pull out the cable on the front side and connect the cable making a loop signal wire Change for fresh air tube 1 Insert the drain hose into the dent of heat insulation materials of indoor unit 2 Insert the indoor outdoor electric cable from backside of indoor unit and pull it out on the front side then ...

Page 5: ...5mm2 HSU 24C03 V ZF Indoor unit Outdoor unit L 1 N 2 HSU 18H03 V ZXF HSU 22H03 V ZXF 1 Two ways for the installation of indoor part as illustrated Way One For all the models In the guard ring connect outlet joint with the fresh air tube Way Two Only for the models of 09 12 Insert the joint of water collecting pan into the fresh air tube then connect the other end of joint with mesh enclosure of wa...

Page 6: ...d cause a leakage of gas Pipe Diameter Liquid side 6 35mm 1 4 Gas side 9 52mm 3 8 Fastening torque Drawing for the installation of indoor and outdoor units Insert the cable according to terminal number in the same manner as the indoor unit Fix the cable with a clamp 18N m 40N m Half union Flare nut Spanner Torque wrench 6 Gas side 12 7mm 1 2 50N m 6 Easily demount cleaning of indoor unit 1 Top inl...

Page 7: ...nding piping air inside piping shall be removed by using external refrigerant gas charge according to the following list Brand new outdoor unit is charged 50g or 80g 22k 24k more refrigerant than regulated weight Only for first installation this extra 50g or 80g 22k 24k can be used to purge airin pipes During this procedure 50g or 80g 22k 24k refrigerant will be discharged in piping This must be s...

Page 8: ...n pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly explain to our customers how to operate through the instruction manual Gas leak from pipe connecting Heat insulation of pipe connecting Are the connecting wirings of indoor and outdoor firmly inserted to ...