SYMPTOM 

ACTION TO TAKE 

1.

 

Mode is Off  (Select Heat, Cool, or Auto) 

Can't Adjust Temperature 

2.

 

Check if thermostat keys are disabled 

To enable thermostat keys for test, remove jumper 

 

SYMPTOM 

ACTION TO TAKE 

  1.  Check COMM connector and wiring 
  2.  Check thermostat address setting 
  3. 

Check communications mode setting 

Control By Remote System 
Not Working 

  4.  Check setup of the remote system 

Ensure that all setup items for the thermostat and the remote system are set to the proper 

configurations for communication 

 

SYMPTOM 

ACTION TO TAKE 

1.

 

Allow 30 minutes for thermostat to adjust to room 

temperature 

2.

 

Adjust calibration offset 

Temperature Reading 
Incorrect 

3.

 

Change setup option to display 

o

F or 

o

After installation, allow the thermostat up to 30 minutes for an accurate temperature reading 

 

SYMPTOM 

ACTION TO TAKE 

Display Problem 

1.

 

Disconnect power to the thermostat.  Reconnect, then 

observe display self-test 

 

For a 5 second period after power is reconnected, all segments of the display should light indicating 

all thermostat functions 

 

SYMPTOM 

ACTION TO TAKE 

1.

 

Heat Pump is not able to meet load due to cold weather 

Aux Heat On Too Often 

2.

 

Thermostat is in EM Heat mode – Set thermostat to Heat or 

Auto mode 

In EM Heat mode, the auxiliary heat is turned on. 

 

SYMPTOM 

ACTION TO TAKE 

Heat Pump Heats In Cool 
Mode & Cools In Heat Mode 

1.

 

Reversing valve is connected to wrong terminal  -  move 

wire from B to O or from O to B 

 

The wires connecting the reversing valve may be reversed - (See Note 1 - Page 8) 

 

SYMPTOM 

ACTION TO TAKE 

No Auxiliary OR Emergency 
Heat 

1.

 

See if heat pump is equipped with outdoor thermostat.  If so, 

disconnect it. 

 

Heat pump may be equipped with an outdoor thermostat which is overriding Aux Heat when 
outdoor temperature is above certain level  -  Disconnect the outdoor thermostat, the RC-100 

controls the Aux Heat automatically 

Summary of Contents for RC-100

Page 1: ...in the country in which this equipment is to be installed INSTALLATION Before installing this thermostat 1 Read all of the installation instructions carefully 2 Read the Owner s Manual carefully 3 Ens...

Page 2: ...ING When mounting the RC 100 grasp the thermostat by the sides avoiding the keys and unsnap the base from the face Holding the base to the wall so that the word TOP is upright and facing you 1 Mark th...

Page 3: ...ation See Figures 7 8 Insert the cable into the connector on the thermostat circuit board marked COMM Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the...

Page 4: ...2 times 2 O Terminal is energized for cooling B Terminal is energized for heating In most applications the reversing valve is energized for cooling and should be connected to the O terminal If the hea...

Page 5: ...5 5 Figure 5...

Page 6: ...2 To configure the display backlight to always be on set the JP2 Select Backlight Mode jumper to the ON position between the middle and bottom pin on the connector See Figure 6 3 To configure the dis...

Page 7: ...o OFF Ensure that the cooling unit goes off If the thermostat or system does not perform as stated above recheck all wiring See Troubleshooting Tips INSTALLER SETUP This section describes the items th...

Page 8: ...ions The thermostat can be configured with the following system options WITH NO EEC EEC 0 8 Auto changeover no fan with heat 1 9 Auto changeover fan on with heat 4 12 Manual changeover no fan with hea...

Page 9: ...s add 16 to each value The default setting is 1 04 Calibration offset This item is used to raise or lower the current temperature reading by 1 degree Fahrenheit or 1 2 degree Celsius If this item is s...

Page 10: ...default setting of 2 degrees F is recommended for all applications In special cases a setting of 3 or 4 may be used when precise control of temperature is not as important as highest energy efficiency...

Page 11: ...cooling system was in operation this week 17 System runtime Last week This item logs the amount of time hours that the heating and cooling system was in operation last week ANTICIPATION RC 100 antici...

Page 12: ...stat has been preprogrammed with energy saving settings recommended under the EPA Energy Star program When used with remote systems HAI recommends that the thermostat be configured as non programmable...

Page 13: ...TCHES The thermostat can be connected to a remote system or remote switch A signal can be sent from the remote location to change the thermostat temperature settings from the DAY setting to the NIGHT...

Page 14: ...stem TROUBLESHOOTING TIPS SYMPTOM ACTION TO TAKE 1 Check power to the thermostat 2 Check wiring diagrams Thermostat Dead 3 Check thermostat temperature sensor Thermostat will not operate with a damage...

Page 15: ...Display Problem 1 Disconnect power to the thermostat Reconnect then observe display self test For a 5 second period after power is reconnected all segments of the display should light indicating all...

Page 16: ...Y W2 HEIL QUAKER 867 PH50 R G O C Y W1 W2 LENNOX HP19 HP20 V VR F R X M Y L LENNOX CB19 R G O C Y W1 L RHEEM RUDD PGB PFA PCB R G O X Y W2 L WEATHERTRON R G O B Y W U YORK E1CS E1FB E1FH R G O B Y W X...

Reviews: