12  Heating minimum on/off time (minutes)

 

 
This item is the same as the “Cooling minimum on/off time”, but for the heating system. 
 
The default setting is 8. 
 

13  Stage 2 Differential 
 

This item specifies the temperature difference between stage 1 and stage 2.  The default setting of 2 (degrees F) 
is recommended for all applications.  In special cases a setting of 3 or 4 may be used when precise control of 
temperature is not as important as highest energy efficiency, however, the thermostat will not be able to 
maintain temperature within 1 degree of its setting under severe weather conditions.  A setting of 1 or 0 is not 
recommended.  The default setting is 2. 
 
In this thermostat, the automatic anticipator will compensate for the temperature "droop" caused by the stage 2 
differential under cold weather conditions. 
 

14 Clock 

adjust

 

 
If the clock on the thermostat is running faster or slower than the actual time, you can have the thermostat 
automatically compensate up to 29 seconds per day.  The thermostat will add or subtract the selected amount of 
time daily. 
 
(1 = “- 29” to 59 = “+ 29” seconds per day; 30 = No change) 
 
The default setting is 30. 

 
Note:  

If an HAI automation system is being used, the controller system time is sent to the thermostat every 

minute.  This adjustment will have no effect. 

 
15 Filter 

reminder

 

 
The thermostat logs the amount of time the system fan has been running.  When this setting reaches 0, the 
thermostat will display a reminder to replace the filter.  The setting is the amount of days (24 hours of system 
operation) before this reminder is displayed. 
 
Days - Counting down from 10 - 0 
 
The filter reminder can be disabled by setting this item to 60. 
 

16  System runtime (This week)

 

 
This item logs the amount of time (hours) that the heating and cooling system was in operation this week. 
 

17  System runtime (Last week)

 

 
This item logs the amount of time (hours) that the heating and cooling system was in operation last week. 

 

 

Summary of Contents for OMNISTAT RC-122BZ

Page 1: ...acceptable in the country in which this equipment is to be installed INSTALLATION Before installing this thermostat 1 Read all of the installation instructions carefully 2 Read the Owner s Manual care...

Page 2: ...NG When mounting the RC 122BZ grasp the thermostat by the sides avoiding the keys and unsnap the base from the face Holding the base to the wall so that the word TOP is upright and facing you 1 Mark t...

Page 3: ...tat push all excess wiring into the hole in the wall Plug the hole with the supplied insulating foam to ensure an accurate temperature reading by the thermostat Align the tabs of the thermostat face w...

Page 4: ...system The display will show all segments for about 5 seconds 3 Press the Fan key The fan should come on Press the Fan key again The fan should go off 4 Press Hold to override Energy Efficient Contro...

Page 5: ...5 5 Figure 5...

Page 6: ...6 2 To configure the display backlight to always be on set the JP2 Select Backlight Mode jumper to the ON position between the middle and bottom pin on the connector See Figure 6 3 To configure the di...

Page 7: ...s item 5 Use the arrow keys to change the value of each item 6 Do not set the values to anything other than the specified range for each item 7 To exit Setup mode press the Fan key The thermostat will...

Page 8: ...cient Control EEC should be turned on settings 0 1 4 and 5 If the system is equipped with a highly efficient second stage you may want to turn EEC off settings 8 9 12 and 13 The thermostat will act li...

Page 9: ...t setting is 51 06 Heat setpoint limit This item is used to limit the temperature setting in heat mode The desired heat setting can never be set above this setting The default setting is 91 07 Not use...

Page 10: ...t is running faster or slower than the actual time you can have the thermostat automatically compensate up to 29 seconds per day The thermostat will add or subtract the selected amount of time daily 1...

Page 11: ...he thermostat QUICK REFERENCE SETUP GUIDE This table displays each Installer Setup item with its default setting The column labeled CURRENT can be used to write down the current settings if any change...

Page 12: ...ry or inclusion controller to exclude the thermostat from the network press and release the Hold button on the thermostat This will exclude the thermostat from the Z Wave network The thermostat suppor...

Page 13: ...LASS_THERMOSTAT_FAN_STATE Upon power up allow 10 seconds for the RC 122BZ thermostat to initialize After 10 seconds a controller can request the state of the fan COMMAND_CLASS_THERMOSTAT_OPERATING_STA...

Page 14: ...15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency...

Page 15: ...stat keys for test remove jumper SYMPTOM ACTION TO TAKE 1 Check Node ID 2 Check communications mode setting Control By Remote System Not Working 3 Check setup of the remote system Ensure that all setu...

Page 16: ...d due to severe weather Stage 2 On Too Often 2 EEC is disabled SYMPTOM ACTION TO TAKE 1 System may be equipped with an outdoor thermostat which is overriding Stage 2 the when outdoor temperature is mi...

Reviews: