HAI OMNISTAT RC-112 Installation Instructions Manual Download Page 1

1

1

 

RC-112 / RC-112B Two Speed Heat Pump 

3 Stage Heat / 2 Stage Cool - With Energy Efficient Control 

 Thermostat Installation Instructions 

 
APPLICATION 
 
This RC-112 thermostat is applicable to heat pumps with two stages of heating and cooling, plus a third stage of 
heating called "auxiliary" heating. The heat pump may have a two-speed compressor (low and high speeds), two 
compressors (stage 1 and stage 2) or a "superheater" or other device as the second stage. In normal operation, 
stage 1 and 2 (or low and high speed) will be used as required to maintain the set temperature. In heating mode, 
the auxiliary heating will only be used if the heat pump cannot maintain a rate of temperature rise with both 
stages running (high speed). 
 
The RC-112 is capable of being controlled both locally and by remote control.  It offers programmability, stand-
alone operation, and robust, optically isolated communications with automation systems, utility control systems, 
and personal computers.  The RC-112B is equipped with a “cool blue” backlight display. 
 
Electrical rating: 

 

24 V; 3 A; 50/60 Hz 

Maximum current: 

 

2 A on any circuit, 3 A total 

Thermostat operating current:  

less than 15 mA 

 
The following requirements must be observed for installation in Europe:  CE 
 

1.

 

This equipment must be installed in accordance with National wiring rules for the country in which it is 
installed. 

2.

 

Fuses must be replaced only with IEC rated components. 

3.

 

All product labels, instructions and markings relating to safety must be translated to a language, which is 
acceptable in the country in which this equipment is to be installed. 

 
INSTALLATION 
 
Before installing this thermostat: 
 

1.

 

Read all of the installation instructions carefully. 

2.

 

Read the Owner's Manual carefully. 

3.

 

Ensure that this product is suitable for your application. 

4.

 

Ensure that wiring complies with all codes and ordinances. 

5.

 

Disconnect power to the control transformer to prevent electrical shock and damage to equipment. 

6.

 

Select an appropriate location to ensure an accurate temperature reading. 

 

Location 

 
When replacing an existing thermostat, install the RC-112 in the same location.  If the existing location doesn't 
meet the following criteria, choose a new location.  When choosing a location for the thermostat: 

 

Document Number 13I00-5 / Rev B / May, 2004 

Copyright 

 1999-2004 Home Automation, Inc. 

All Rights Reserved

 

Summary of Contents for OMNISTAT RC-112

Page 1: ...m current 2 A on any circuit 3 A total Thermostat operating current less than 15 mA The following requirements must be observed for installation in Europe CE 1 This equipment must be installed in acco...

Page 2: ...sting thermostat 3 Disconnect the wires going to each terminal on the thermostat Label each wire with the letter or number at the terminal 4 Remove the existing plate or base from the wall MOUNTING Wh...

Page 3: ...ation See Figures 7 8 Insert the cable into the connector on the thermostat circuit board marked COMM Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the...

Page 4: ...s energized for cooling B Terminal is energized for heating In most applications the reversing valve is energized for cooling and should be connected to the O terminal If the heat pump requires the re...

Page 5: ...5 5 Figure 5...

Page 6: ...2 To configure the display backlight to always be on set the JP2 Select Backlight Mode jumper to the ON position between the middle and bottom pin on the connector See Figure 6 3 To configure the dis...

Page 7: ...at the cooling unit goes off Note As a convenience to the installer the compressor start up protection delay can be canceled To cancel the delay press the Prog key 3 times then press the Fan key 2 tim...

Page 8: ...ured with the following system options WITH NO EEC EEC 0 8 Auto changeover no fan with heat 1 9 Auto changeover fan on with heat 4 12 Manual changeover no fan with heat 5 13 Manual changeover fan on w...

Page 9: ...isplays add 16 to each value The default setting is 1 04 Calibration offset This item is used to raise or lower the current temperature reading by 1 degree Fahrenheit or 1 2 degree Celsius If this ite...

Page 10: ...nimum time set by this item When the cooling system turns off it must remain off for a minimum time set by this item Setting Cycles per hour maximum 5 6 6 5 7 4 8 3 7 10 3 The recommended setting is 8...

Page 11: ...system operation before this reminder is displayed Days Counting down from 10 0 The filter reminder can be disabled by setting this item to 60 16 System runtime This week This item logs the amount of...

Page 12: ...This thermostat has been preprogrammed with energy saving settings recommended under the EPA Energy Star program When used with remote systems HAI recommends that the thermostat be configured as non p...

Page 13: ...TCHES The thermostat can be connected to a remote system or remote switch A signal can be sent from the remote location to change the thermostat temperature settings from the DAY setting to the NIGHT...

Page 14: ...piece of tape Figure 8 Hookup to remote Day Night setback switch OTHER SYSTEMS For connections to personal computers utility management systems and other automation systems refer to connection diagra...

Page 15: ...at keys for test remove jumper SYMPTOM ACTION TO TAKE 1 Check COMM connector and wiring 2 Check thermostat address setting 3 Check communications mode setting Control By Remote System Not Working 4 Ch...

Page 16: ...Reversing valve is connected to wrong terminal move wire from B to O or from O to B The wires connecting the reversing valve may be reversed See Note 2 Page 4 SYMPTOM ACTION TO TAKE No Auxiliary OR Em...

Reviews: