tebis
TX 025
auto
2-200 lux
200-20 000 lux
230 V
8
6
test
604025
0
EE002 / EE003
8
6
TX 025
8
6
TX 025
8
6
TX 025
8
6
TX 025
Light sensitive switch
User instructions
GB
A warranty period of 24 months is offered on hager products,
from date of manufacture, relating to any material of manufac-
turing defect. If any product is found to be defective it must be
returned via the installer and supplier (wholesaler). The warran-
ty is withdrawn if :
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary to
IEE wiring regulations and accepted practice within the industry
at the time of installation.
- the procedure for the return of goods has not been followed.
Explanation of defect must be included when returning goods.
Warranty
GB
✂
F
D
GB
NL
3
tebis
TX 025
604025
o
aut
o
test
2-200
lux
200-20
000
lux
TX 025, TX 026
Electrical connection
Chaining of TX 025 units
6T 7210.a
F
D
GB
NL
Safety Recommendations:
- Installation should only be carried
out by a suitably qualified electrician.
- Observe the installation regulations
of the protection measures SELV.
Bu
s EIB 29
V
Physical addressing
push-button and LED
Lux selector
indicators
➁ ➂
Auto / Manu / Test
switch
➀
Technical Specifications
Electrical characteristics
●
Supply voltage: bus EIB 29 V
●
Maximum connection distance of
probe:100m.
Functional characteristics
●
Operating range:
2 to 200 lux
200 to 20000 lux
Environment
●
TX 025 : Operating T° :
0 °C to +45 °C
●
Probe :
Operating T° : - 30 °C to +60 °C
●
TX 025 : Storage T° :
- 20 °C to +70 °C
●
Probe :
Storage T° :
- 30 °C to +70 °C
Connection
●
Capacity:
flexible: 1 mm
2
to 6 mm
2
rigid: 1,5 mm
2
to 10 mm
2
●
Probe:
Use dual insulation cable for connecting
wall-mounted sensor EE 003 or for
extending cable of flush-mounted sensor
EE 002.
Dimensions
●
Size: 2 modules.
Installation recommendations
1. Install the module at the bottom of enclosure to
prevent excessive operating temperature.
2. Connect module to bus EIB.
3. Connect probe EE 002 or EE 003 if necessary.
4. Follow the instructions of system requirements.
Operating principle
This product is mainly intended for automatic
control of inside/outside lighting circuits
(ON/OFF and dimming controls) and blinds or
rolling shutters according to ambient lighting
level.
Associated with an external probe, this light-
sensitive switch measures natural lighting
and controls circuits according to a preset
threshold range of 2 to 20000 lux.
Several light sensitive switches may be
chained to increase the number of channels.
In this case, only one probe is connected to
one of the light sensitive switches.
Kit TX 026
Kit TX026 includes:
- 1 light sensitive switch TX 025
- 1 wall-mounted light sensor EE 003.
Setting lighting threshold
After configuration:
1. Set switch
➀
to the test position (threshold
2. Press push-button
➅
(one of indicators
➁
or
➂
lights on) to select the gauge
(2... 200 lux or 200... 20000 lux).
3. Switch back auto/manu/test switch
to the desired mode
4. Set switch
➀
to "test" position;
at the selected moment of the day, turn the
setting potentiometer
➃
up to the switching
threshold (indicator light
➄
switches on).
5. Set back switch
➀
into "auto" position, as
the normal operating mode of equipment.
Compatible lighting probes
- Flush-mounted light sensor EE 002
- Wall-mounted light sensor EE 003.
Indicator light displays
Switch
➀
set to auto or test position
Indicator signalling threshold
Indicator light goes on when the value measured is lower
underrange
than threshold set.
Indicator for selecting gauge
Indicator
➁
is on when gauge 2 … 200 lux is selected.
Indicator
➂
is on when gauge 200 … 20000 lux is selected.
Indicators
➁
and
➂
flicker alternately when probe is not
connected or faulty.
Examples of lighting levels
Lighting Conditions
Average lighting lux value
Full moon
< 1 lux
Bright street light at night
20 … 70 lux
Very cloudy sky
1500 … 2000 lux
Cloudy sky
4000 … 5000 lux
Outside shaded area
10000 … 15000 lux
Sunshine
> 15000 lux
➃
Potentiometer for setting
lighting threshold
➄
Indicator signalling
threshold underrange
➅
Push-button
Lighting probe
EE 002 or EE 003
TX 025 unit
with
probe
TX 025 unit
without
probe
5. To ensure a good working of the light sensitive
switch, the lighting probe must not be influenced
by artificial light or direct solar radiation and has
to be sheltered from dust and humidity.
Hager Electro S.A.S. - 132, bld d’Europe - BP3 - 67 215 Obernai cedex - Tél. 03.88.49.50.50 - www.hager.com