G
B
Installing the detector
Smoke detectors
Recommende
d location
d > 50 cm
60
c
m
>
d
>
5
0
cm
d > 50 cm
Acceptable
location
Fig. 1
Fig. 2
Make sure there is a distance of at least 2 meters between each product, except between two detectors.
Choosing the right place
The detector must be placed:
●
in rooms where there is a risk of fire (living
rooms with a fireplace, children’s bedrooms,
lofts or basements that are occupied),
●
preferably at the center of the ceiling,
●
at a distance from ventilation grilles where
smoke might spread,
●
more than 50 cm away from obstacles
(walls, partitions, beams, etc.),
●
at either end of corridors more than 10 m
long.
If the smoke detector cannot be installed at a
horizontal ceiling, mount it:
●
more than 50 cm away from the corners of
the room (Fig. 1),
●
50 to 60 cm away from the ceiling (Fig. 1),
●
far away from potential sources of electri-
cal interference (electricity meter, metal cabi-
net, etc.),
●
if it is to be installed on a metal wall, insert
a shim made of non-magnetic material
(wood or plastic).
Installation examples:
The detector must not be placed:
●
directly on a metal surface,
●
near fluorescent tubes,
●
in very dusty rooms,
●
in rooms where the temperature could drop
below -10°C or rise above +55°C, as this will
prevent the detector from operating properly,
●
less than 1 m away from heating, cooling
or ventilation grilles likely to spread smoke,
●
less than 6 m away from a fireplace or
wood-burning stove where combustion
fumes could cause untimely alarms,
●
in premises where cooking fumes and
steam could result in untimely triggering,
●
in premises where there is a risk of con-
densation or humidity (bathrooms, laundries,
etc.),
●
at the top of pointed (A-shaped) ceilings as
an air pocket at this point could prevent
smoke from reaching the detector (Fig. 2).
Mounting examples:
35
Summary of Contents for S151-22X
Page 47: ...G B 47...