50
Operation
Navigation in the menus
Parameters access :
Press “up”, “down”, “left” & “right” push buttons
•
Parameter modification:
press “right” push button to access the parameter to modify
Press “up’’ and “down” push buttons to modify the parameter and “validate”
•
Return to main menu:
press “ESC” push button Value is only modified after validation
Programming access
• Step 1:
press and hold for 5s“validation” push button
•
Step 2:
enter code (factory code =1000) using navigation push buttons
•
Step 3:
press validation push button
Programming exit
• Press and hold for 5s “validation” push button
Programming :
• This mode allows product parameters configuration
• Always accessible in position
• Always accessible in AUT position, changeover switch on priority source, priority source being available
• Not accessible when “test off load”, “test on load” and“control” functions are active or during automatic sequence.
q
Parameters requiring programming before use:
• type of network
• nominal voltage
• and nominal frequency.