5

6LE001152A.f

3

Auto confi guration of mains voltage and frequency

The  product  includes  an  “Auto  Confi guration” 

feature to detect the mains voltage and 

frequency nominal values, phase rotation and 

neutral position and saves them in the ATS 

controller.

Note

Before  confi guring  the  nominal  values  ensure 

that the product is properly wired, verifi ed and 

ready for commissioning. It is imperative that 

the network supply is available and that the 

wiring to the product voltage sensing terminals 

103 – 106 and 203 – 206 has been done. It is 

preferable to use the product sensing kit that 

may be provided as an accessory.
•  Ensure that the product is in manual mode and 

powered with Pot1 in position “Auto Conf”.

•   Press and hold the Red “PROG OK” button 

for >2s to measure the mains voltage and 

frequency.

Note

The  source  available  LED  will  fl ash  while  the 

available network is being measured. The 

READY LED will fl ash green as soon as settings 

are measured and until these settings have 

been saved by pressing the PROG OK button a 

second time momentarily (refer to Step   ).

4

Saving the confi gured values

To SAVE the recorded setting confi guration 

press the PROG OK button momentarily: 

<60ms.

Note

The fl ashing READY LED goes off once the 

values are saved in the ATS controller.

5

Putting the product into Auto operation

After following Steps 1 to 4, and once ready to 

put the product into AUTO operation turn the 

mode selector switch to Auto.

Note

When the product is powered and properly 

confi gured,  after  switching  the  product  from 

Manual Mode to Auto Mode the READY light 

should be a steady green light.

< 60ms.

Depending on the state of the product the ATS automation may change the 

switch position as soon as the mode selector is switched to AUT. This is a 

normal operation.

> 2s.