5
6LE001152A.f
3
Auto confi guration of mains voltage and frequency
The product includes an “Auto Confi guration”
feature to detect the mains voltage and
frequency nominal values, phase rotation and
neutral position and saves them in the ATS
controller.
Note
Before confi guring the nominal values ensure
that the product is properly wired, verifi ed and
ready for commissioning. It is imperative that
the network supply is available and that the
wiring to the product voltage sensing terminals
103 – 106 and 203 – 206 has been done. It is
preferable to use the product sensing kit that
may be provided as an accessory.
• Ensure that the product is in manual mode and
powered with Pot1 in position “Auto Conf”.
• Press and hold the Red “PROG OK” button
for >2s to measure the mains voltage and
frequency.
Note
The source available LED will fl ash while the
available network is being measured. The
READY LED will fl ash green as soon as settings
are measured and until these settings have
been saved by pressing the PROG OK button a
second time momentarily (refer to Step ).
4
Saving the confi gured values
To SAVE the recorded setting confi guration
press the PROG OK button momentarily:
<60ms.
Note
The fl ashing READY LED goes off once the
values are saved in the ATS controller.
5
Putting the product into Auto operation
After following Steps 1 to 4, and once ready to
put the product into AUTO operation turn the
mode selector switch to Auto.
Note
When the product is powered and properly
confi gured, after switching the product from
Manual Mode to Auto Mode the READY light
should be a steady green light.
< 60ms.
Depending on the state of the product the ATS automation may change the
switch position as soon as the mode selector is switched to AUT. This is a
normal operation.
> 2s.