System-disconnection relay EU400 NA-protection
11
Subject to technical changes
Default settings and firmware version, TOR Erzeuger Typ A,B,C,D,
VSE NA/EEA-NE7 CH 2020, G98(83/2)+G99(G59/3), Synergrid C10 / C11
When changing programs, all parameters are reset to the default settings.
Menu
Parameter / Unit
Default settings
TOR
Erzeuger
Typ
A,B,C,D**
VSE
NA/EEA-
NE7
CH 2020
G98(G83/2) + G99(G59/3)
Synergrid
C10/C11
3AC+N
230V
3AC+N
230V
3/2/1A
C+N
230V *
3AC
400V *
3AC+N
63,5V *
3AC
110V *
3AC+N
230V
Pr10
Pr15
Pr20
Pr21
Pr22
Pr23
Pr16
U¯ ¯
59.S2
59>S2
U¯ ¯
Alarm on/off
on
on
on
on
on
on
on
U¯ ¯
Overvoltage
V
264
276
273
476
71.7
124
264
H¯ ¯
Hysteresis
V
13.3
23.0
5.0
5.0
1.0
1.0
5.0
dAL
Response time
s
0.10
0.10
0.50
0.50
0.50
0.50
0.05
doF
OFF-delay
s
60
60
20
20
20
20
1
U¯
59.S1
59>S1
U¯
Alarm on/off
on
oFF
on
on
on
on
on
U¯
Overvoltage
V
255
253
262
456
69.8
121
253
H¯
Hysteresis
V
4.3
3.0
5.0
5.0
1.0
1.0
5.0
dAL
Response time
s
60.0
60.0
1.00
1.00
1.00
1.00
1.00
doF
OFF-delay
s
60
60
20
20
20
20
1
UՈ¯
59-Av
UՈ
Alarm on/off
on
on
oFF
oFF
oFF
oFF
oFF
UՈ
Overvoltage
V
255
253
262
456
65.8
121
253
HՈ
Hysteresis
V
4.3
3.0
5.0
5.0
1.0
1.0
5.0
dAL
Response time
s
0.10
0.10
1.00
1.00
1.00
1.00
1.00
doF
OFF-delay
s
60
60
20
20
20
20
1
U_
27.S1
27<S1
U_
Alarm on/off
on
on
oFF
oFF
oFF
oFF
on
U_
Undervoltage
V
184
184
200
348
50.2
95.7
161
H_
Hysteresis
V
11.5
12.0
5.0
5.0
1.0
1.0
5.0
dAL
Response time
s
1.00
1.50
2.50
2.50
2.50
2.50
1.50
doF
OFF-delay
s
60
60
20
20
20
20
1
U_ _
27.S2
27<S2
U_ _
Alarm on/off
on
on
on
on
on
on
on
U_ _
Undervoltage
V
69.0
104
184
320
50.8
88.0
57.0
H_ _
Hysteresis
V
126.5
92.0
5.0
5.0
1.0
1.0
5.0
dAL
Response time
s
0.20
0.30
2.50
2.50
2.50
2.50
0.05
doF
OFF-delay
s
60
60
20
20
20
20
1
F¯ ¯
81.S2
81>S2
F¯ ¯
Alarm on/off
oFF
oFF
on
on
on
on
oFF
F¯ ¯
Overfrequency
Hz
51.50
51.50
52.00
52.00
52.00
52.00
51.50
H¯ ¯
Hysteresis
Hz
1.40
2
1.40
2
1.95
1
1.95
1
1.95
1
1.95
1
1.40
2
dAL
Response time
s
0.10
0.10
0.50
0.50
0.50
0.50
0.05
doF
OFF-delay
s
60
60
20
20
20
20
1
F¯
81.S1
81>S1
F¯
Alarm on/off
on
on
oFF
oFF
oFF
oFF
on
F¯
Overfrequency
Hz
51.50
51.50
51.50
51.50
51.50
51.50
51.50
H¯
Hysteresis
Hz
1.40
2
1.40
2
1.45
1
1.45
1
1.45
1
1.45
1
1.40
2
dAL
Response time
s
0.10
0.10
90.0
90.0
90.0
90.0
0.05
doF
OFF-delay
s
60
60
20
20
20
20
1
*
8
pr20
8
…
8
Pr23
8
for 240/416 V rated voltage change settings of: Voltage x (240V / 230 V)
**
8
pr10
8
the ÖVE / ÖNORM E 8001-4-712 can be parameterized by adapting the parameters
1
= Autohysteresis 50.05 Hz
2
= Autohysteresis 50.10 Hz
Display of the program:
8
Info
8
→
8
Pr
8
or when switching on
Display of the firmware version:
8
Info
8
→
8
Fnr
8