EC370, EC372

§

Three phase kWh meter, 
measure via CT 50 to 6000 A

User instructions

®

´

®

Contador de energia trifásico,
medida via TI de 50 a 6000A

Instruções de instalação

Apresentação

A

Ecrã LCD.

B

Tecla para o desfile dos valores.

C

Tecla “prog” para parametrizar o calibre do T.I. e o tipo
de rede.

D

Reset para colocar a zero o contador parial.

E

LED metrológico (1 Wh = 10 impulsos).

Parametrização do contador

Os seguintes parâmetros tem de ser definidos antes da 
colocação em serviço do contador : 
- Calibre do TI.
- Tipo de rede (mono ou trifásica com / sem neutro).
- Tipo de instalação em trifásico (equilibrado ou não

equilibrado).

1. Para entrar no modo parametrização, efectuar uma

pressão longa (3 seg.) na tecla Prog.

2. O ajuste do calibre do TI é visualizado (100A). Com

pressões sucessivas na tecla "B", fazer desfilar os dife-
rentes valores de TI possíveis (50, 100, 150, 200, 250,
300, 400, 600, 800… 6000A).

3. Pressionar a tecla "Prog" para validar e passar para o

parâmetro seguinte.

4. O tipo de rede (1L+N, 2L, 3L, 3L+N) é visualizado.

Com pressões sucessivas na tecla "leitura" fazer desfilar
os diferentes valores e seleccionar o tipo de rede.

5. Pressionar a tecla "Prog" para validar e passar para o

parâmetro seguinte.

6. Para as instalações trifásicas, o tipo de instalação  

visualiza-se "Equilibrado/ Não Equilibrado" (Bl, Unbl).
Com pressões na tecla "B" fazer desfilar os valores e
seleccionar o tipo da instalação.

7. Pressionar a tecla "Prog" para validar.

8. Para sair do modo programação; exercer uma pressão

longa (3 seg.) na tecla Prog.

Leitura dos valores

Com pressões sucessivas na tecla "leitura", fazer desfilar
os diferentes valores.
Por defeito, o contador indica a energia activa consumida
na tarifa em uso.

EC370 :

1

1

a

pressão : Ligar da retroiluminação.

Consumo de energia activa total (kWh).

2

2

a

pressão : consumo de energia activa parcial (kWh).

3

3

a

pressão : consumo de energia reactiva total (kVARh).

Product presentation

A

LCD display.

B

Key to scroll readings.

C

"Prog" key to set up the CT ratio and the type of  
network.

D

Reset to reset the partial counter.

E

Metrological LED (1 Wh = 10 impulses).

Meter setup 

The following settings have to be made before the meter
can be put to use : 
- CT ratio.
- Type of network (single or three-phase). 
- Type of three-phase installation (balanced or unbalanced).

1. Press the Prog key during 3 sec. to enter the set-up

mode.

2. The CT ratio setting is displayed (100A). Press the key

"Read" repeatedly to scroll the possible CT values
(50, 100, 150, 200, 250, 300, 400, 600, 800… 6000A).

3. Press "Prog" to confirm and switch to the next setting.
4. The type of network (1L+N, 2L, 3L, 3L+N) is displayed. 

Press the key "Read" repeatedly to scroll the possible
values and select the type of network.

5. Press "Prog" to confirm and switch to the next setting. 

6. On three-phase installations, the type of installation is

displayed as "Balanced/Unbalanced" (Bl, Unbl). 
Press the key "Read" to scroll the values and select
the type of installation. 

7. Press "Prog" to confirm. 

8. Press the Prog key during 3 sec. to exit the programming

mode.

Display of readings

The various datas can be scrolled by pressing the Key
"Read".

The Default display will indicate power consumption   
according to the current tariff.

EC370 :

1

1st pressure : backlight switches ON. 
Total active energy consumption (kWh).

2

2nd pressure : partial active energy consumption (kWh).

3

3rd pressure : total reactive energy consumption
(kVAR).

4

4th pressure : partial reactive energy consumption
(kVAR).

5

5th pressure : instant power consumption (kW).

EC372 :

The EC372 provides detailed display of the total/   
partial active energy consumptions according to tariff
(T1 or T2) and in total (T).

To reset the partial meter

- Press the scrolling key several times in order to 

display partial energy.

- Press the reset button during 3 sec.

The partial meters (active and reactive energy) will be
set to zero.

Note :

The information 

on the display indicates that

the corresponding phase (1, 2,3) is under voltage.

Connection test and error displaying 

The energymeter must be under voltage and the
measured circuit must be loaded.
Press the "reading" key during 3s to enter into the
connection test mode.

Err 0

= no error

Err 1

= CT phase 1 inverted

Err 2

= CT phase 2 inverted

Err 3

= CT phase 3 inverted

Err 4

= V1 and V2 voltages inverted

Err 5

= V2 and V3 voltages inverted

Err 6

= V3 and V1 voltages inverted

Err 7

= V1 and N inverted

Err 8

= V2 and N inverted

Err 9

= V3 and N inverted.

Press the "reading" key during 3s to leave the
connection test mode.

Note :

The CT connection polarity is not taken into account
by the energymeter.
The information 

Err 1

/

Err 2

/

Err 3

is only for informa-

tion purposes.

Note :

In installations set as “unbalanced”, install one CT
per phase. 
In installations set as “balanced”, install one CT on 
phase 1. 

Technical specifications

Metrological characteristics

- Accuracy class B (1%) according to EN50470-3
- Metrological LED : 

1 impuls = 0.1 Wh x CT ratio. For example in an installa-
tion with CT 100/5A, one impuls = 0.1 Wh x 20 = 2Wh.

- Starting current : 10 mA
- Basic current : 5 A
- Max current : 6 A

Technical characteristics 

- Consumption : < 0,6 W et 2,8 VA max per phase
- Supply : 230/400 V

+/- 15%

- Frequency : 50/60 Hz +/- 2 Hz

- Savings of measures are made regularly and in case

of power failure in EEPROM

- Characteristic of tariff input EC372 : 

tariff 1 = 0 V, tariff 2 = 230 V

+/- 15%

- Impulse output characteristics : 

• 1 pulse : 100 Wh 
• Pulse duration : 100 ms 
• External supply : 20 ... 30 V 

Mechanical characteristics

- Modular casing 4 M (72 mm)
- Protection degree (casing) : IP20
- Insulation class : II

Environment

- Storage temperature : -25 °C to +70 °C
- Working temperature : -10 °C to +55 °C
- Connection capacity :

• flexible :

1 à 6 mm

2

• rigid

:

1,5 à 10 mm

2

Operating principle

This kilowatt hour meter measures the active and reactive electrical energy used in an electrical installation.
This device has a digital LCD to display energy used and power.
This device has a total counter and a partial resettable counter.
In case of two tariff levels, the EC372 will count separetely the energy used in tariff 1 and in tariff 2.

Nota :

para as instalações parametrizadas como "não 
equilibrada", ligar 1 TI por fase.
Para as instalações parametrizadas como "equilibradas",
ligar apenas um TI, na fase 1.

Especificações técnicas
Características metrológicas

Classe de precisão B (1%) conforme 

EN50470-3

LED metrológico

1 impulso = 0,1 Wh x relação do TI; 
por exemplo, numa instalação com TI 100/5A, 
1 impulso = 0,1 Wh x 20 = 2 Wh

- Corrente de arranque : 10 mA 
- Corrente de base : 5 A
- Corrente Máx : 6 A

Características eléctricas

- Consumo : < 0,6 W & 2,8 VA max por fase
- Alimentação : 230/400 V

+/- 15%

- Frequência : 50/60 Hz +/- 2 Hz
- Salvaguarda periódica das medidas e em caso de

corte de rede na memória EEPROM

- Característica entrada tarifa : tarifa 1 = 0 V  

tarifa 2 = 30 V

+/- 15%

- Características saída impulso :

• Valor do impulso fixo : 100 Wh 
• Duração de impulso : 100 ms 
• Tensão de alimentação (externa) : 20 ... 30 V 

Características mecânicas

- Caixa modular de largura 4 M (72 mm)
- Índice de protecção caixa : IP20
- Classe de isolamento : II

Ambiente

- T

a

de armazenamento : -25 °C a + 70 °C

- T

a

de funcionamento : -10 °C a + 55 °C

- Capacidade de ligação  :

• Flexível : 1 a 6 mm

2

• Rígido : 1,5 a 10 mm

2

Princípio de funcionamento

O contador de energia mede a energia eléctrica activa e reactiva consumida por um circuito eléctrico.
Está equipado com um ecrã LCD que permite visualizar a energia consumida e a potência.
Está equipado com um contador totalizador e um contador parcial com retorno a zero.
O EC372 permite, ainda, repartir o consumo de energia activa em dois tipos de tarifa diferentes.

Hager SAS - 132 bld d’Europe - BP 78 - 67 212 Obernai cedex (FRANCE) - Tél. +333 88 49 50 50 - www.hagergroup.net

EC370, EC372

Edition 10/10 - IS 

877071-C

/ RECTO-VERSO / S blanc of

fset  80g/m² / I Pantone Black 

Important 

This function can only be used if the 
installation power factor is between 
0.6 and 1.

4

4

a

pressão : consumo de energia reactiva parcial

(kVARh).

5

5

a

pressão : potência instantânea.

EC372 :

O EC372 detalha os consumos de energia activas
totais e parciais por tarifa (T1 ou T2) e no total (T).

Reposição a zero do contador parcial

- Pressionar a tecla B a fim de visualizar no ecrã uma

energia parcial.

- Fazer uma pressão prolongada (3 seg.) no botão

reset.

Os contadores parciais são reposto a zero.

Observação :

A informação 

no ecrã indica que a fase corres-

pondente (1, 2,3) está sob tensão.

Testes de ligação e verificação
de erros

O contador de energia tem de estar alimentado e o
circuito a medir deve estar ligado.
Pressionar a tecla de B durante 3 seg. para entrar no
modo teste.

Err 0

= sem erros

Err 1

= TI fase 1 invertido

Err 2

= TI fase 2 invertido

Err 3

= TI fase 3 invertido

Err 4

= Tensões V1 e V2 invertidas

Err 5

= Tensões V2 e V3 invertidas

Err 6

= Tensões V3 e V1 invertidas

Err 7

= Tensão V1 e N invertidos

Err 8

= Tensão V2 e N invertidos

Err 9

= Tensão V3 e N invertidos

Pressionar a tecla B durante 3 seg. para sair do
modo teste. 

Nota

A polaridade da ligação do TI não é considerada
pelo contador de energia.
A informação 

Err 1/Err 2/Err

3 é meramente

informativa.

Atenção

Esta função só pode ser usada em
instalações com um factor de potência
entre 0,6 e 1.

 