HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

DAMPER INSTALLATION – SEPARATED WALLS

1. Installation sleeve

     

For installation in light stud walls, use an installation  
sleeve or a similar approved seal and caulking for the  
duct lead-through.

The sleeve supplied by HAGAB is in two parts and is  
adapted to fit in the hole for each damper size. 

Fit the parts together from each direction against the wall/
structural element and screw them together. Maximum 
thickness of the structural element is 180 mm.

2. Install the duct

 

Centre the duct against the installation sleeve. Suspension 
devices for the duct must match the fire resistance rating of 
the structural element. 

See for example the Svensk Ventilation/HVAC Technical 
Association’s manual “Practical solutions for fire protection 
and ventilation”. 

Fit the space between the installation sleeve and  
connecting duct with fireproof insulation made of  
mineral wool or an equivalent sealant.

INTACT

 

Fire/Fire gas damper

D + 50 mm