General Specification
Enclosure
Steel IP30. Epoxy powder coated Interpon Radon, silver grey
Cabling
Fire resistant screened cable, minimum size 1mm
2
. Max cable
length 1Km (20 Ohm). Fire Burn, FP200 or equivalent (max
capacitance 1uF, max inductance 1 millihenry).
Temperature range: -5°C to +40°C
Maximum Relative Humidity: 95%
Number of conventional detection
circuits
3 for single flood zone area. 6 for dual flood zone area
Works with following conventional
detectors
Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
Approx. dimensions of panel
(W x H x D)
363 x 310 x 85(mm) (Single Flood Zone)
436 x 396 x 150 (mm) (Two Flood Zones)
Power Supply Specification
Mains supply
10% / -15% 50Hz max
current 0.74Amp (35W) for
Single flood zone
10% / -15% 50Hz max
current 2.1 Amp (100W) for Dual
flood zone
Mains supply fuse
2 Amp (T2A 250V) 35W unit
4 Amp (T4A 250V) 100W unit
Not accessible for servicing. Internal
to switched mode power unit
Power supply rating
1.2 Amps total including battery
charging for single flood zone
3.4 Amps total including battery
charging for single and dual flood
zones
Maximum load shared between
outputs = 1 Amp single flood zone, 3
Amp single and dual flood zones
Power supply output voltage 19.8 - 29.7VDC
Tol/- 0.1%
Maximum continuous load
for battery standby (I max A)
I max A = 650mA for single flood
zone
I max A = 930mA for single and
dual flood zone
I max B not specified
Minimum current drawn by
panel
Single Flood Zone = 168mA
Single and Dual Flood Zone =
240mA
Maximum ripple voltage
150 mV p-p (Both single and
dual)
Supply and charger fault monitored