![Hach RTC105 Basic User Manual Download Page 23](http://html1.mh-extra.com/html/hach/rtc105/rtc105_basic-user-manual_576768023.webp)
Table 26 RTC105 N/DN-module (2-channels with DO option) (continued)
Tag name
Parameter
Unit
Channel
Description
ACTUAT VAR 5
A_S 1
%
1
Aeration intensity VFD 1
ACTUAT VAR 6
A_S 2
%
1
Aeration intensity VFD 2
ACTUAT VAR 7
B_S 2
Stage
2
Aeration stage (ON/OFF) B_S 2
ACTUAT VAR 8
Nreg 2
—
2
Internal calculation value Nreg
ACTUAT VAR 9
Oreg 2
—
2
Internal calculation value Oreg
ACTUAT VAR 10
A_S 1
%
2
Aeration intensity VFD 1
ACTUAT VAR 11
A_S 2
%
2
Aeration intensity VFD 2
ACTUAT VAR 12
Osetp 1
mg/L
1
O
2
set point
ACTUAT VAR 13
Osetp 2
mg/L
2
O
2
set point
Table 27 RTC113 ST-module and RTC112 SD-module (1-channel)
Tag name
Parameter Unit Channel Description
MEASUREMENT 1 Qin 1
L/s
1
Actual flow rate to thickening
MEASUREMENT 2 Qavg 1
L/s
1
Averaged flow rate to thickening (as defined in menu)
MEASUREMENT 3 Qdos 1
L/h
1
Quantity of polymer added
MEASUREMENT 4 Tsin 1
g/L
1
TS concentration in inflow (modified by averaging).
MEASUREMENT 5 Tsef 1
g/L
1
TS concentration in effluent (modified by averaging and
hopper pump operation).
ACTUAT VAR 6
Pdos 1
L/h
1
Calculated set point for polymer flow
ACTUAT VAR 7
Fac 1
g/kg 1
Calculated polymer quantity (g/kg)
ACTUAT VAR 8
Feed 1
L/s
1
Calculated feed flow rate
Table 28 RTC113 ST-module and RTC112 SD-module (2-channels)
Tag name
Parameter Unit Channel Description
MEASUREMENT 1
Qin 1
L/s
1
Actual flow rate to thickening
MEASUREMENT 2
Qavg 1
L/s
1
Averaged flow rate to thickening (as defined in menu)
MEASUREMENT 3
Qdos 1
L/h
1
Quantity of polymer added
MEASUREMENT 4
Tsin 1
g/L
1
TS concentration in inflow (modified by averaging).
MEASUREMENT 5
Tsef 1
g/L
1
TS concentration in effluent (modified by averaging and
hopper pump operation).
MEASUREMENT 6
Qin 2
L/s
2
Actual flow rate to thickening
MEASUREMENT 7
Qavg 2
L/s
2
Averaged flow rate to thickening
MEASUREMENT 8
Qdos 2
L/h
2
Quantity of polymer added
MEASUREMENT 9
Tsin 2
g/L
2
TS concentration in inflow (modified by averaging).
MEASUREMENT 10 Tsef 2
g/L
2
TS concentration in effluent (modified by averaging and
hopper pump operation).
ACTUAT VAR 11
Pdos 1
L/h
1
Calculated set point for polymer flow
ACTUAT VAR 12
Fac 1
g/kg 1
Calculated polymer quantity (g/kg)
English
23
Summary of Contents for RTC105
Page 503: ......