Figure 8 AC power connections
Table 1 AC wiring information (AC models only)
Connection
Color—North America
Color—EU, UK, AU
Hot (L)
Black
Brown
Neutral (N)
White
Blue
Protective earth ground (G)
Green
Green with yellow stripe
Connect a backup battery
W A R N I N G
Explosion and fire hazard. Battery substitution is not permitted. Use only batteries that are supplied by
the instrument manufacturer.
Connect a backup battery to AC units to keep a supply of power to the instrument during a power
outage. Refer to
Accessories
on page 43. The external AC power charges the backup battery. If
the AC power stops, the backup battery supplies power to the instrument.
For safety, obey all battery precautions and warnings. Discard the battery in accordance with local,
regional and national regulations.