28
Parameterization and operation
MIN RECIRCULATION
Note: 0/4 to20 mA input can be used either for Qreci or for Qras.
Minimum recirculation flow rate according to measurement signal
corresponding to 0/4mA
[L/s]
MAX RECIRCULATION
Note: 0/4 to20 mA input can be used either for Qreci or for Qras.
Maximum recirculation flow rate of influent according to
measurement signal corresponding to 20mA
[L/s]
0/4 to 20 mA
Note: 0/4 to20 mA input can be used either for Qreci or for Qras.
Transfer range of 0/4 to 20 mA current loop as set in connected flow
measuring instrument.
Note: The input is not connected to the 0/4 to 20 mA has to be
calculated in ratio to Qinflow.
Q RECI RATIO
Note: 0/4 to20 mA input can be used either for Qreci or for Qras.
If the value Q RECI RATIO is “0” the RECI flow is calculated bases
on the mA input signal.
If the value is different from “0” the RECI flow is calculated from the
inflow:
Q RECI= Q RECI RATIO * INFLOW
within the limits of MIN RECIRCULATION and MAX
RECIRCULATION.
[%]
MIN RETURN SLUDGE
Note: 0/4 to20 mA input can be used either for Qreci or for Qras.
Minimum return sludge flow rate according to measurement signal
corresponding to 0/4mA
[L/s]
MAX RETURN SLUDGE
Note: 0/4 to20 mA input can be used either for Qreci or for Qras.
Maximum return sludge flow rate of influent according to
measurement signal corresponding to 20mA
[L/s]
0/4 to 20 mA
Note: 0/4 to20 mA input can be used either for Qreci or for Qras.
Transfer range of 0/4 to 20 mA current loop as set in connected flow
measuring instrument.
Q RETURN RATIO
Note: 0/4 to20 mA input can be used either for Qreci or for Qras.
If the value Q RETURN RATIO is “0” the RAS flow is calculated
bases on the mA input signal.
If the value is different from “0” the RAS flow is calculated from the
inflow:
Q RETURN = Q RETURN RATIO * INFLOW
within the limits of MIN RETURN SLUDGE and MAX RETURN
SLUDGE.
[%]
VOLUME
VOLUME
Aerated volume
[m
3
]
4.4.2
1-Channel RTC103 N-Module Stages (Continued)
RTC MODULES / PROGNOSYS
RTC MODULES
RTC
Summary of Contents for RTC103 N-Module
Page 2: ......
Page 6: ...6 Table of Contents ...
Page 14: ...14 General Information ...
Page 20: ...20 Installation ...
Page 54: ...54 Maintenance ...
Page 56: ...56 Troubleshooting ...
Page 58: ...58 Replacement parts and accessories ...
Page 62: ...62 Warranty and liability ...
Page 64: ...64 MODBUS address setting ...
Page 66: ...66 Index ...