background image

 

Please read through these operating instructions carefully. You will be informed about the function and handling of 
this stove and you will also save fuel and conserve the environment by heating correctly.  
The attached 

equipment sheet

 is part of these operating instructions. 

1.  General information 

 

Please check the appliance for transport damage when unpacking it. In case of defects, please report 
these immediately to your stove dealer! 

 

National and European standards, local regulations and those under building law as well as the relevant 
state building regulations or fire regulations must be complied with when installing, connecting and putting 
the fireplace into operation. 

 

The pellet stove described in these instructions has been tested according to DIN EN14785 and 
according to the electrical standard, DIN EN 60335-2-102.  

2.  General safety information 

 

The combustion of fuels releases heat energy, which leads to the surfaces of the heating appliance (e.g. 
doors, inspection window panes, side walls, front wall, flue tube) heating up significantly. 

 

The appliance starts independently in "Standby mode". Due to the build-up of heat on the window pane, 
care should be taken that no unsupervised persons, who do not know how to operate the pellet stove, are 
in the installation room. 

 

Air extraction equipment such as ventilation systems, extractor hoods, vented tumble dryers etc. or other 
fireplaces must not have a disruptive influence on the air supply for the stove. 

 

During operation, the combustion air opening provided must not be closed, throttled, constricted, covered 
or shut off. 

 

On stoves with an outdoor air connection, the opening must not be shut or closed during operation. 

 

Make children aware of these dangers and keep them away from the fireplace when it is in heating mode. 

 

The  combustion  chamber  door  must  only  be  opened  for  cleaning  and  maintenance  purposes  when  in 
“Off” mode. Otherwise this should always be kept closed.  

 

The pellet stove may only be connected to the mains after being properly connected to the fireplace. 

 

The protective grille in the pellet container must not be removed.  

 

The pellet stove must only be operated when the tank cap is closed. 

 

Never use liquid fuels to ignite the pellet stove or to revive existing embers. 

 

Do not place any laundry items on the stove to dry! 

 

When  operating  your  heating  appliance,  it  is  forbidden  to  work  with  highly  combustible  and  explosive 
materials in the same or adjoining rooms! 

 
 

The stove must not be set up to be operated jointly with the home’s air conditioning and ventilation units. 

 

Exceptions:  

RLU certified appliances can also be operated with extractor hoods, vented tumble dryers and air conditioning and 
ventilation units if the stove has also been connected to a balanced flue. 

3.  Electrical connection 

 

The stove is operated with a mains voltage of 230V 50Hz. The average power consumption is 50-60 
Watts. During the ignition phase, the power consumption can increase to 400 Watts.  

 

Only use the original mains cable supplied with the appliance 

 

The socket must be easily accessible. 

4.  Chimney  

The  chimney  should  be  made  e.g.  of  stainless  steel  or  ceramic  (glazed  inside)  so  that  it  cannot  become 

contaminated from soot and damp. This is necessary due to the low flue gas temperature of your pellet stove. 

 

Please observe the national regulations. 

Summary of Contents for HSP 6 PALLAZZA-III 519.08

Page 1: ...PELLET STOVE Nameplate Aufstellungs und Bedienungsanleitung Pelletofen DE Fiche descritive Poele FR Schema tecnica strufa Camino IT Equipment sheet Fireplace GB Tshnicki podaci Kaminsku HR Podatkovni...

Page 2: ...8 2 Energy saving mode ACTUAL room temperature display 9 8 3 Button lock child safety device 9 9 Functions in the main menu 9 9 1 Main menu Select functions 9 9 1 1 Operating mode Week program Settin...

Page 3: ...tricted covered or shut off On stoves with an outdoor air connection the opening must not be shut or closed during operation Make children aware of these dangers and keep them away from the fireplace...

Page 4: ...flue tube does not stick out into the open cross section of the chimney which would interfere with the flue gases rising and prevent the optimal cleaning of the chimney The use of wall lagging is rec...

Page 5: ...recommended to feed the cold air into the room from outside via a direct duct as this can lead to the build up of condensation In order to guarantee a sufficient supply of air the duct should not be l...

Page 6: ...iameter Identification DINplus Norm M 7135 ENplus A1 7 2 Unsuitable fuels The use of lower quality or unauthorised fuel adversely affects the operation of your pellet stove and may lead to the lapse o...

Page 7: ...its mounting Close the combustion chamber door Fill the storage container with pellets Plug in mains cable Tip Only when using for the first time place approx 30 pellets in the burner This speeds up t...

Page 8: ...er until it reaches the necessary flame temperature and only then switches to the cooling operating status and then OFF During the first use odours may build up for a short time Please ensure that the...

Page 9: ...ctivation Hold the Menu button down for approx 10 seconds until Button block activated no longer appears on the display 9 Functions in the main menu 9 1 Main menu Select functions OK language english...

Page 10: ...tch on time can now be set with the Plus or Minus buttons The switch off time on the respective week day can be programmed by pressing the right hand arrow button The required room temperature is sele...

Page 11: ...with the Plus or Minus buttons The setting is saved by pressing the OK button To exit the function press the On Off button 9 1 4 Heating curve How it works h003 OK 2 2 main menu heating curve set fac...

Page 12: ...given on the WLAN module operating instructions 9 1 7 Fill manually Optional only on HSP8 on screw conveyor off main menu Fill manually Procedure Place the cursor in the main menu on Fill manually Pr...

Page 13: ...the START of the respective test setting 10 Operating statuses 10 1 Start Zone 1 20 Start phase The start phase begins if the current room temperature falls below the set target temperature by 1 C the...

Page 14: ...CO mode Eco mode means continuous operation at a low output if the ACTUAL room temperature is higher than the set TARGET room temperature i e the stove does not switch off but continues to run on a sm...

Page 15: ...p battery so that data is retained during a power cut A distinction is made between a short power cut and a long power cut Short power cut The short cut lasts for less than about 30 seconds Once the e...

Page 16: ...tive G Pellet fuel has too low a calorific value A Clean burner B Clean burner fill pellet tank C Clean the intake on the screw conveyor housing with a vacuum cleaner Clean burner D Clean burner Ensur...

Page 17: ...alorific value E Downpipe screw conveyor blocked F Room too airtight required combustion air cannot flow into the room G Flame temperature sensor defective H Screw motor defective A Fill pellet tank B...

Page 18: ...eals seals of any kind handles invalidate a warranty Maintenance or cleaning not performed or performed inadequately a flue draft that is incorrectly set to the appliance or is insufficient or too hig...

Reviews: