
87
c.
(Optional.) Use a T15 Torx screwdriver to lock the locking lever, as shown by callout 3
in
.
Figure 119 Installing the access panel
4.
Rack-mount the server. For more information, see "
."
5.
Connect the power cord. For more information, see "
6.
Power on the server. For more information, see "
Replacing a power supply
The power supplies are hot swappable.
If two power supplies are installed and sufficient space is available for replacement, you can replace
a power supply without powering off or removing the server from the rack.
Procedure
1.
Power off the server. For more information, see "
2.
Remove the server from the rack. For more information, see "
Removing the server from a rack
."
3.
Remove the power cord from the power supply:
a.
Press the tab to disengage the ratchet from the tie mount, slide the cable clamp outward,
and then release the tab, as shown by callouts 1 and 2 in
b.
Open the cable clamp and remove the power cord out of the clamp, as shown by callouts 3
and 4 in
c.
Unplug the power cord, as shown by callout 5 in